SIEMENS
8/6
Siemens KT 10.1 · 2016
8
■
Technical specifications
(continued)
SITOP in the SIMATIC Design
1-phase, 24 V DC (for S7-300 and ET200M)
Article number
6ES7307-1EA01-0AA0
6ES7307-1EA80-0AA0
6ES7307-1KA02-0AA0
Product
PS 307
PS 307 Outdoor
PS 307
Power supply, type
24 V/5 A
24 V/5 A
24 V/10 A
Input
Input
1-phase AC
1-phase AC
1-phase AC
Supply voltage
• 1 at AC Rated value
120 V
120 V
120 V
• 2 at AC Rated value
230 V
230 V
230 V
• Note
Automatic range selection
Set by means of selector switch on
the device
Automatic range selection
Input voltage
• 1 at AC
85 ... 132 V
93 ... 132 V
85 ... 132 V
• 2 at AC
170 ... 264 V
187 ... 264 V
170 ... 264 V
Wide-range input
No
No
No
Overvoltage resistance
2.3 ×
V
in rated
, 1.3 ms
2.3 ×
V
in rated
, 1.3 ms
2.3 ×
V
in rated
, 1.3 ms
Mains buffering at
I
out rated
, min.
20 ms; at
V
in
= 93/187 V
20 ms; at
V
in
= 93/187 V
20 ms; at
V
in
= 93/187 V
Rated line frequency 1
50 Hz
50 Hz
50 Hz
Rated line frequency 2
60 Hz
60 Hz
60 Hz
Rated line range
47 ... 63 Hz
47 ... 63 Hz
47 ... 63 Hz
Input current
• at rated input voltage 120 V
2.3 A
2.1 A
4.2 A
• at rated input voltage 230 V
1.2 A
1.2 A
1.9 A
• at rated input voltage 24 V
-
-
-
• at rated input voltage 110 V
-
-
-
Switch-on current limiting (+25 °C), max.
20 A
45 A
55 A
Duration of inrush current limiting at 25 °C
• maximum
3 ms
3 ms
3 ms
I²t, max.
1.2 A²·s
1.8 A²·s
3.3 A²·s
Built-in incoming fuse
T 3,15 A/250 V
(not accessible)
T 3,15 A/250 V
(not accessible)
T 6.3 A/250 V
(not accessible)
Protection in the mains power input (IEC 898)
Recommended miniature circuit
breaker: from 6 A characteristic C
Recommended miniature circuit
breaker: from 10 A characteristic C
or from 6 A characteristic D
Recommended miniature circuit
breaker: from 10 A characteristic C
Output
Output
Controlled, isolated DC voltage
Controlled, isolated DC voltage
Controlled, isolated DC voltage
Rated voltage
V
out
DC
24 V
24 V
24 V
Total tolerance, static ±
3 %
3 %
3 %
Static mains compensation, approx.
0.1 %
0.2 %
0.1 %
Static load balancing, approx.
0.5 %
0.4 %
0.5 %
Residual ripple peak-peak, max.
50 mV
150 mV
50 mV
Residual ripple peak-peak, typ.
10 mV
40 mV
15 mV
Spikes peak-peak, max.
(bandwidth: 20 MHz)
150 mV
240 mV
150 mV
Spikes peak-peak, typ.
(bandwidth: 20 MHz)
20 mV
90 mV
60 mV
Product function
Output voltage adjustable
No
No
No
Output voltage setting
-
-
-
Status display
Green LED for 24 V OK
Green LED for 24 V OK
Green LED for 24 V OK
On/off behavior
No overshoot of
V
out
(soft start)
No overshoot of
V
out
(soft start)
No overshoot of
V
out
(soft start)
Startup delay, max.
2 s
3 s
2 s
Voltage rise, typ.
10 ms
100 ms
10 ms
Rated current value
I
out rated
5 A
5 A
10 A
Current range
0 ... 5 A
0 ... 5 A
0 ... 10 A
• Note
Supplied active power typical
120 W
120 W
240 W
Short-term overload current
• on short-circuiting during the start-up typical
20 A
20 A
38 A
• at short-circuit during operation typical
20 A
20 A
38 A
Duration of overloading capability for excess
current
• on short-circuiting during the start-up
100 ms
180 ms
80 ms
• at short-circuit during operation
100 ms
80 ms
80 ms
Parallel switching for enhanced performance
Yes
No
Yes
© Siemens AG 2016