SIEMENS
6/10
Siemens KT 10.1 · 2016
6
■
Technical specifications
(continued)
SITOP modular
1- and 2-phase, 24 V DC
Efficiency
Efficiency at
V
out rated
,
I
out rated
,
approx.
88 %
88 %
91 %
91 %
Power loss at
V
out rated
,
I
out rated
,
approx.
17 W
17 W
24 W
24 W
Power loss [W] during no-load
operation maximum
4 W
4 W
6 W
6 W
Closed-loop control
Dynamic mains compensation
(
V
in rated
±15 %), max.
0.1 %
0.1 %
0.1 %
0.1 %
Dynamic load smoothing
(
I
out
: 50/100/50 %),
U
out
± typ.
3 %
3 %
3 %
3 %
Load step setting time
50 to 100 %, typ.
2 ms
2 ms
2 ms
2 ms
Load step setting time
100 to 50 %, typ.
2 ms
2 ms
2 ms
2 ms
Setting time maximum
5 ms
5 ms
5 ms
5 ms
Protection and monitoring
Output overvoltage protection
< 35 V
< 35 V
< 35 V
< 35 V
Current limitation, typ.
6 A
6 A
12 A
12 A
Property of the output
Short-circuit proof
Yes
Yes
Yes
Yes
Short-circuit protection
Alternatively, constant
current characteristic
approx. 5.5 A or latching
shutdown
Alternatively, constant
current characteristic
approx. 5.5 A or latching
shutdown
Alternatively, constant
current characteristic
approx. 12 A or latching
shutdown
Alternatively, constant
current characteristic
approx. 12 A or latching
shutdown
Enduring short circuit current
RMS value
• typical
6 A
6 A
12 A
12 A
Overload/short-circuit indicator
LED yellow for "overload",
LED red for "latching
shutdown"
LED yellow for "overload",
LED red for "latching
shutdown"
LED yellow for "overload",
LED red for "latching
shutdown"
LED yellow for "overload",
LED red for "latching
shutdown"
Safety
Primary/secondary isolation
Yes
Yes
Yes
Yes
Galvanic isolation
Safety extra-low output
voltage
U
out
acc. to
EN 60950-1 and EN 50178
Safety extra-low output
voltage
U
out
acc. to
EN 60950-1 and EN 50178
Safety extra-low output
voltage
U
out
acc. to
EN 60950-1 and EN 50178
Safety extra-low output
voltage
U
out
acc. to
EN 60950-1 and EN 50178
Protection class
Class I
Class I
Class I
Class I
Leakage current
• maximum
3.5 mA
3.5 mA
3.5 mA
3.5 mA
• typical
0.25 mA
0.25 mA
0.32 mA
0.32 mA
CE mark
Yes
Yes
Yes
Yes
UL/cUL (CSA) approval
cULus-Listed (UL 508,
CSA C22.2 No. 107.1),
File E197259
cULus-Listed (UL 508,
CSA C22.2 No. 107.1),
File E197259
cULus-Listed (UL 508,
CSA C22.2 No. 107.1),
File E197259
cULus-Listed (UL 508,
CSA C22.2 No. 107.1),
File E197259
Explosion protection
IECEx Ex nA nC IIC T4 Gc;
ATEX (EX) II 3G Ex nA nC IIC
T4 Gc (for AC 120-230/
230-400 V); cCSAus
(CSA C22.2 No. 213,
ANSI/ISA-12.12.01) Class I,
Div. 2, Group ABCD, T3
IECEx Ex nA nC IIC T4 Gc;
ATEX (EX) II 3G Ex nA nC IIC
T4 Gc (for AC 120-230/
230-400 V); cCSAus
(CSA C22.2 No. 213,
ANSI/ISA-12.12.01) Class I,
Div. 2, Group ABCD, T3
IECEx Ex nA nC IIC T4 Gc;
ATEX (EX) II 3G Ex nA nC IIC
T4 Gc (for AC 120-230/
230-400 V); cCSAus
(CSA C22.2 No. 213,
ANSI/ISA-12.12.01) Class I,
Div. 2, Group ABCD, T3
IECEx Ex nA nC IIC T4 Gc;
ATEX (EX) II 3G Ex nA nC IIC
T4 Gc (for AC 120-230/
230-400 V); cCSAus
(CSA C22.2 No. 213,
ANSI/ISA-12.12.01) Class I,
Div. 2, Group ABCD, T3
CB approval
Yes
Yes
Yes
Yes
Marine approval
GL, ABS
GL
GL, ABS
GL, ABS
Degree of protection (EN 60529)
IP20
IP20
IP20
IP20
Article number
6EP1333-3BA10
6EP1333-3BA10-8AC0
6EP1334-3BA10
6EP1334-3BA10-8AB0
Product
SITOP PSU200M
SITOP PSU200M
with protective coating
SITOP PSU200M
SITOP PSU200M
with protective coating
Power supply, type
24 V/5 A
24 V/5 A
24 V/10 A
24 V/10 A
© Siemens AG 2016