SIEMENS
6/9
Siemens KT 10.1 · 2016
6
■
Technical specifications
(continued)
SITOP modular
1- and 2-phase, 24 V DC
Input current
• at rated input voltage 120 V
2.2 A
2.2 A
4.4 A
4.4 A
• at rated input voltage 230 V
1.2 A
1.2 A
2.4 A
2.4 A
• at rated input voltage 500 V
0.61 A
0.61 A
1.1 A
1.1 A
Switch-on current limiting (+25 °C),
max.
35 A
35 A
35 A
35 A
I²t, max.
1.7 A²·s
1.7 A²·s
4 A²·s
4 A²·s
Built-in incoming fuse
T 3.15 A (not accessible)
T 3.15 A (not accessible)
T 6.3 A (not accessible)
T 6.3 A (not accessible)
Protection in the mains power input
(IEC 898)
Recommended miniature
circuit breaker at 1-phase
operation: from 6 A (10 A)
characteristic C (B); required
at 2-phase operation:
circuit breaker 2-pole
connected or circuit breaker
3RV2011-1EA10 (setting
3.8 A) or 3RV2711-1ED10
(UL 489) at 230 V;
3RV2011-1DA10 (setting
3 A) or 3RV2711-1DD10
(UL 489) at 400/500 V
Recommended miniature
circuit breaker at 1-phase
operation: from 6 A (10 A)
characteristic C (B); required
at 2-phase operation:
circuit breaker 2-pole
connected or circuit breaker
3RV2011-1EA10 (setting
3.8 A) or 3RV2711-1ED10
(UL 489) at 230 V;
3RV2011-1DA10 (setting
3 A) or 3RV2711-1DD10
(UL 489) at 400/500 V
Recommended miniature
circuit breaker at 1-phase
operation: from 6 A (10 A)
characteristic C (B); required
at 2-phase operation: circuit
breaker 2-pole connected
or circuit breaker
3RV2011-1EA10 (setting
3.8 A) or 3RV2711-1ED10
(UL 489) at 230 V;
3RV2011-1DA10 (setting
3 A) or 3RV2711-1DD10
(UL 489) at 400/500 V
Recommended miniature
circuit breaker at 1-phase
operation: from 6 A (10 A)
characteristic C (B); required
at 2-phase operation: circuit
breaker 2-pole connected
or circuit breaker
3RV2011-1EA10 (setting
3.8 A) or 3RV2711-1ED10
(UL 489) at 230 V;
3RV2011-1DA10 (setting
3 A) or 3RV2711-1DD10
(UL 489) at 400/500 V
Output
Output
Controlled, isolated DC
voltage
Controlled, isolated DC
voltage
Controlled, isolated DC
voltage
Controlled, isolated DC
voltage
Rated voltage
V
out
DC
24 V
24 V
24 V
24 V
Total tolerance, static ±
3 %
3 %
3 %
3 %
Static mains compensation, approx.
0.1 %
0.1 %
0.1 %
0.1 %
Static load balancing, approx.
0.1 %
0.1 %
0.1 %
0.1 %
Residual ripple peak-peak, max.
50 mV
50 mV
50 mV
50 mV
Spikes peak-peak, max.
(bandwidth: 20 MHz)
200 mV
200 mV
200 mV
200 mV
Adjustment range
24 ... 28.8 V
24 ... 28.8 V
24 ... 28.8 V
24 ... 28.8 V
Product function Output voltage
adjustable
Yes
Yes
Yes
Yes
Output voltage setting
via potentiometer
via potentiometer
via potentiometer
via potentiometer
Status display
Green LED for 24 V OK
Green LED for 24 V OK
Green LED for 24 V OK
Green LED for 24 V OK
Signaling
Relay contact (NO contact,
rating 60 V DC/ 0.3 A) for
"24 V OK"
Relay contact (NO contact,
rating 60 V DC/ 0.3 A) for
"24 V OK"
Relay contact (NO contact,
rating 60 V DC/ 0.3 A) for
"24 V OK"
Relay contact (NO contact,
rating 60 V DC/ 0.3 A) for
"24 V OK"
On/off behavior
Overshoot of
V
out
approx.
3 %
Overshoot of
V
out
approx.
3 %
Overshoot of
V
out
approx.
3 %
Overshoot of
V
out
approx.
3 %
Startup delay, max.
1 s
1 s
1 s
1 s
Voltage rise, typ.
50 ms
50 ms
50 ms
50 ms
Rated current value
I
out rated
5 A
5 A
10 A
10 A
Current range
0 ... 5 A
0 ... 5 A
0 ... 10 A
0 ... 10 A
• Note
-
-
+60 ... +70 °C: Derating
2%/K (at 120 V, 230 V) or
3.5%/K (at 400 V)
+60 ... +70 °C: Derating
2%/K (at 120 V, 230 V) or
3.5%/K (at 400 V)
Supplied active power typical
120 W
120 W
240 W
240 W
Short-term overload current
• at short-circuit during operation
typical
15 A
15 A
30 A
30 A
Duration of overloading capability for
excess current
• at short-circuit during operation
25 ms
25 ms
25 ms
25 ms
Constant overload current
• on short-circuiting during the
start-up typical
6 A
6 A
12 A
12 A
Parallel switching for enhanced
performance
Yes; switchable
characteristic
Yes; switchable
characteristic
Yes; switchable
characteristic
Yes; switchable
characteristic
Numbers of parallel switchable units
for enhanced performance
2
2
2
2
Article number
6EP1333-3BA10
6EP1333-3BA10-8AC0
6EP1334-3BA10
6EP1334-3BA10-8AB0
Product
SITOP PSU200M
SITOP PSU200M
with protective coating
SITOP PSU200M
SITOP PSU200M
with protective coating
Power supply, type
24 V/5 A
24 V/5 A
24 V/10 A
24 V/10 A
© Siemens AG 2016