SIEMENS
6/5
Siemens KT 10.1 · 2016
6
■
Technical specifications
(continued)
SITOP modular
1-phase, 24 V DC
Efficiency
Efficiency at
V
out rated
,
I
out rated
,
approx.
93 %
94 %
93 %
88 %
Power loss at
V
out rated
,
I
out rated
,
approx.
9 W
18 W
42 W
131 W
Power loss [W] during no-load
operation maximum
1.5 W
1.5 W
-
-
Closed-loop control
Dynamic mains compensation
(
V
in rated
±15 %), max.
0.1 %
0.1 %
0.5 %
1 %
Dynamic load smoothing
(
I
out
: 50/100/50 %),
U
out
± typ.
2 %
4 %
1 %
2 %
Load step setting time
50 to 100 %, typ.
0.25 ms
0.25 ms
1 ms
2 ms
Load step setting time
100 to 50 %, typ.
0.5 ms
0.5 ms
1 ms
2 ms
Dynamic load smoothing
(
I
out
: 10/90/10 %),
U
out
± typ.
2 %
4 %
-
-
Load step setting time
10 to 90%, typ.
0.25 ms
0.25 ms
-
-
Load step setting time
90 to 10%, typ.
0.5 ms
0.5 ms
-
-
Setting time maximum
1 ms
1 ms
5 ms
5 ms
Protection and monitoring
Output overvoltage protection
< 33 V
< 33 V
< 33 V
< 35 V
Current limitation, typ.
6 A
12 A
21.5 A
46 A
Property of the output
Short-circuit proof
Yes
Yes
Yes
Yes
Short-circuit protection
Alternatively, constant current
characteristic approx. 6 A or
latching shutdown
Alternatively, constant current
characteristic approx. 12 A
or latching shutdown
Alternatively, constant current
characteristic approx. 23 A
or latching shutdown
Alternatively, constant current
characteristic approx. 46 A
or latching shutdown
Enduring short circuit current
RMS value
• typical
6 A
12 A
23 A
46 A
Overcurrent overload capability in
normal operation
overload capability
150 %
I
out rated
up to 5 s/min
overload capability
150 %
I
out rated
up to 5 s/min
overload capability
150 %
I
out rated
up to 5 s/min
Overload/short-circuit indicator
LED yellow for "overload",
LED red for "latching
shutdown"
LED yellow for "overload",
LED red for "latching
shutdown"
LED yellow for "overload",
LED red for "latching
shutdown"
LED yellow for "overload",
LED red for "latching
shutdown"
Safety
Primary/secondary isolation
Yes
Yes
Yes
Yes
Galvanic isolation
Safety extra-low output
voltage
U
out
acc. to
EN 60950-1 and EN 50178
Safety extra-low output
voltage
U
out
acc. to
EN 60950-1 and EN 50178
Safety extra-low output
voltage
U
out
acc. to
EN 60950-1 and EN 50178
Safety extra-low output
voltage
U
out
acc. to
EN 60950-1 and EN 50178
Protection class
Class I
Class I
Class I
Class I
Leakage current
• maximum
3.5 mA
3.5 mA
3.5 mA
3.5 mA
• typical
1 mA
1 mA
1 mA
0.4 mA
CE mark
Yes
Yes
Yes
Yes
UL/cUL (CSA) approval
cULus-Listed (UL 508,
CSA C22.2 No. 107.1),
File E197259, cCSAus
(CSA C22.2 No. 60950-1,
UL 60950-1, UL 1604)
cULus-Listed (UL 508,
CSA C22.2 No. 107.1),
File E197259, cCSAus
(CSA C22.2 No. 60950-1,
UL 60950-1, UL 1604)
cULus-Listed (UL 508,
CSA C22.2 No. 107.1),
File E197259
cULus-Listed (UL 508,
CSA C22.2 No. 107.1),
File E197259
Explosion protection
IECEx Ex nA nC IIC T4 Gc;
ATEX (EX) II 3G Ex nA nC IIC
T4 Gc; cCSAus (CSA C22.2
No. 213, ANSI/ISA-12.12.01)
Class I, Div. 2, Group ABCD,
T3
IECEx Ex nA nC IIC T4 Gc;
ATEX (EX) II 3G Ex nA nC IIC
T4 Gc; cCSAus (CSA C22.2
No. 213, ANSI/ISA-12.12.01)
Class I, Div. 2, Group ABCD,
T3
IECEx Ex nA nC IIC T3 Gc;
ATEX (EX) II 3G Ex nA nC IIC
T3 Gc; cCSAus (CSA C22.2
No. 213, ANSI/ISA-12.12.01)
Class I, Div. 2, Group ABCD,
T3
IECEx Ex nA IIC T3 Gc;
ATEX (EX) II 3G Ex nA IIC T3
Gc; cCSAus (CSA C22.2
No. 213, ANSI/ISA-12.12.01)
Class I, Div. 2, Group ABCD,
T3
FM approval
-
-
-
-
CB approval
Yes
Yes
No
No
Marine approval
GL, ABS
GL, ABS
GL, ABS
-
Degree of protection (EN 60529)
IP20
IP20
IP20
IP20
Article number
6EP3333-8SB00-0AY0
6EP3334-8SB00-0AY0
6EP1336-3BA10
6EP1337-3BA00
Product
SITOP PSU8200
SITOP PSU8200
SITOP PSU8200
SITOP PSU100M
Power supply, type
24 V/5 A
24 V/10 A
24 V/20 A
24 V/40 A
© Siemens AG 2016