SIEMENS
3/13
Siemens KT 10.1 · 2016
3
LOGO!Power
1-phase, 24 V DC
■
Technical specifications
Article number
6EP1331-1SH03
6EP1332-1SH43
6EP1332-1SH52
Product
LOGO!Power
LOGO!Power
LOGO!Power
Power supply, type
24 V/1.3 A
24 V/2.5 A
24 V/4 A
Input
Input
1-phase AC or DC
1-phase AC or DC
1-phase AC or DC
Rated voltage value
V
in rated
100 ... 240 V
100 ... 240 V
100 ... 240 V
Voltage range AC
85 ... 264 V
85 ... 264 V
85 ... 264 V
Input voltage
• at DC
110 ... 300 V
110 ... 300 V
110 ... 300 V
Wide-range input
Yes
Yes
Yes
Overvoltage resistance
2.3 ×
V
in rated
, 1.3 ms
2.3 ×
V
in rated
, 1.3 ms
2.3 ×
V
in rated
, 1.3 ms
Mains buffering at
I
out rated
, min.
40 ms; at
V
in
= 187 V
40 ms; at
V
in
= 187 V
40 ms; at
V
in
= 187 V
Rated line frequency 1
50 Hz
50 Hz
50 Hz
Rated line frequency 2
60 Hz
60 Hz
60 Hz
Rated line range
47 ... 63 Hz
47 ... 63 Hz
47 ... 63 Hz
Input current
• at rated input voltage 120 V
0.7 A
1.22 A
1.95 A
• at rated input voltage 230 V
0.35 A
0.66 A
0.97 A
Switch-on current limiting (+25 °C),
max.
25 A
46 A
30 A
I²t, max.
0.8 A²·s
3 A²·s
2.5 A²·s
Built-in incoming fuse
internal
internal
internal
Protection in the mains power input
(IEC 898)
Recommended miniature circuit
breaker: from 16 A characteristic B
or from 10 A characteristic C
Recommended miniature circuit
breaker: from 16 A characteristic B
or from 10 A characteristic C
Recommended miniature circuit
breaker: from 16 A characteristic B
or from 10 A characteristic C
Output
Output
Controlled, isolated DC voltage
Controlled, isolated DC voltage
Controlled, isolated DC voltage
Rated voltage
V
out
DC
24 V
24 V
24 V
Total tolerance, static ±
3 %
3 %
3 %
Static mains compensation, approx.
0.1 %
0.1 %
0.1 %
Static load balancing, approx.
1.5 %
1.5 %
1.5 %
Residual ripple peak-peak, max.
200 mV
200 mV
200 mV
Residual ripple peak-peak, typ.
10 mV
10 mV
30 mV
Spikes peak-peak, max.
(bandwidth: 20 MHz)
300 mV
300 mV
300 mV
Spikes peak-peak, typ.
(bandwidth: 20 MHz)
20 mV
50 mV
60 mV
Adjustment range
22.2 ... 26.4 V
22.2 ... 26.4 V
22.2 ... 26.4 V
Product function Output voltage
adjustable
Yes
Yes
Yes
Output voltage setting
via potentiometer
via potentiometer
via potentiometer
Status display
Green LED for output voltage OK
Green LED for output voltage OK
Green LED for output voltage OK
On/off behavior
No overshoot of
V
out
(soft start)
No overshoot of
V
out
(soft start)
No overshoot of
V
out
(soft start)
Startup delay, max.
0.5 s
0.5 s
0.5 s
Voltage rise, typ.
15 ms
10 ms
15 ms
Rated current value
I
out
rated
1.3 A
2.5 A
4 A
Current range
0 ... 1.3 A
0 ... 2.5 A
0 ... 4 A
• Note
+55 ... +70 °C: Derating 2%/K
+55 ... +70 °C: Derating 2%/K
+55 ... +70 °C: Derating 2%/K
Supplied active power typical
30 W
60 W
96 W
Parallel switching for enhanced
performance
Yes
Yes
Yes
Numbers of parallel switchable units
for enhanced performance
2
2
2
© Siemens AG 2016