SIEMENS
3/10
Siemens KT 10.1 · 2016
3
■
Technical specifications
(continued)
LOGO!Power
1-phase, 15 V DC
Output
Output
Controlled, isolated DC voltage
Controlled, isolated DC voltage
Rated voltage
V
out
DC
15 V
15 V
Total tolerance, static ±
3 %
3 %
Static mains compensation, approx.
0.1 %
0.1 %
Static load balancing, approx.
1.5 %
1.5 %
Residual ripple peak-peak, max.
200 mV
200 mV
Residual ripple peak-peak, typ.
10 mV
10 mV
Spikes peak-peak, max.
(bandwidth: 20 MHz)
300 mV
300 mV
Spikes peak-peak, typ. (bandwidth: 20 MHz)
30 mV
70 mV
Adjustment range
10.5 ... 16.1 V
10.5 ... 16.1 V
Product function Output voltage adjustable
Yes
Yes
Output voltage setting
via potentiometer
via potentiometer
Status display
Green LED for output voltage OK
Green LED for output voltage OK
On/off behavior
No overshoot of
V
out
(soft start)
No overshoot of
V
out
(soft start)
Startup delay, max.
0.5 s
0.5 s
Voltage rise, typ.
15 ms
15 ms
Rated current value
I
out rated
1.9 A
4 A
Current range
0 ... 1.9 A
0 ... 4 A
• Note
+55 ... +70 °C: Derating 2%/K
+55 ... +70 °C: Derating 2%/K
Supplied active power typical
23 W
50 W
Parallel switching for enhanced performance
Yes
Yes
Numbers of parallel switchable units for
enhanced performance
2
2
Efficiency
Efficiency at
V
out rated
, I
out rated
, approx.
81 %
85 %
Power loss at
V
out rated
, I
out rated
, approx.
7 W
11 W
Power loss [W] during no-load operation
maximum
2 W
2.3 W
Closed-loop control
Dynamic mains compensation
(
V
in
rated ±15 %), max.
0.2 %
0.2 %
Dynamic load smoothing (
I
out
: 10/90/10 %),
U
out
± typ.
2.8 %
3 %
Load step setting time 10 to 90%, typ.
1 ms
1 ms
Load step setting time 90 to 10%, typ.
1 ms
1 ms
Protection and monitoring
Output overvoltage protection
Yes, according to EN 60950-1
Yes, according to EN 60950-1
Current limitation, typ.
2.7 A
5.7 A
Property of the output Short-circuit proof
Yes
Yes
Short-circuit protection
Constant current characteristic
Constant current characteristic
Enduring short circuit current RMS value
• maximum
3.6 A
7 A
Overload/short-circuit indicator
-
-
Safety
Primary/secondary isolation
Yes
Yes
Galvanic isolation
Safety extra-low output voltage
U
out
acc. to
EN 60950-1 and EN 50178
Safety extra-low output voltage
U
out
acc. to
EN 60950-1 and EN 50178
Protection class
Class II (without protective conductor)
Class II (without protective conductor)
CE mark
Yes
Yes
UL/cUL (CSA) approval
cULus-Listed (UL 508, CSA C22.2 No. 107.1),
File E197259; cURus-Recognized (UL 60950,
CSA C22.2 No. 60950), File E151273, NEC class 2
(acc. to UL 1310)
cULus-Listed (UL 508, CSA C22.2 No. 107.1), F
ile E197259; cURus-Recognized (UL 60950,
CSA C22.2 No. 60950), File E151273, NEC class 2
(acc. to UL 1310)
Explosion protection
ATEX (EX) II 3G Ex nA IIC T3; cCSAus (CSA C22.2
No. 213-M1987, ANSI/ISA-12.12.01-2007) Class I,
Div. 2, Group ABCD, T4
ATEX (EX) II 3G Ex nA IIC T3; cCSAus (CSA C22.2
No. 213-M1987, ANSI/ISA-12.12.01-2007) Class I,
Div. 2, Group ABCD, T4
FM approval
Class I, Div. 2, Group ABCD, T4
Class I, Div. 2, Group ABCD, T4
CB approval
Yes
Yes
Marine approval
GL, ABS
GL, ABS
Degree of protection (EN 60529)
IP20
IP20
Article number
6EP1351-1SH03
6EP1352-1SH03
Product
LOGO!Power
LOGO!Power
Power supply, type
15 V/1.9 A
15 V/4 A
© Siemens AG 2016