SIEMENS
15/16
Siemens KT 10.1 · 2016
15
■
Overview
(continued)
Technical information and configuration
Fusing of the output circuit 24 V DC, selectivity
I
out rated
: Rated output current
I
out dyn
: Dynamic overcurrent with short-circuit during operation
: instantaneous tripping, as dynamic overcurrent on short-circuit
> limit current of electromagnetic tripping.
•: instantaneous tripping probable, as dynamic overcurrent on short-
circuit at least 50% within tolerance range of the tripping characteristic.
X: no instantaneous tripping.
Article No.
I
out rated
I
out dyn.
Characteristic B
6 A
10 A
13 A
16 A
6EP1332-2BA20
2.5 A
9 A/
800 ms
X
X
X
X
6EP1333-2BA20
5 A
18 A/
800 ms
X
X
x
X
6EP1333-3BA10
5 A
15 A/
25 ms
X
X
X
X
6EP3333-8SB00-0AY0
5 A
15 A/
25 ms
X
X
X
X
6EP1334-2BA20
10 A
32 A/
1000 ms
•
X
X
X
6EP1334-3BA10
10 A
30 A/
25 ms
•
X
X
X
6EP3334-8SB00-0AY0
10 A
30 A/
25 ms
•
X
X
X
6EP1434-2BA10
10 A
16 A/
100 ms
X
X
X
X
6EP1336-2BA10
20 A
35 A/
100 ms
•
X
X
X
6EP3436-8SB00-0AY0
20 A
60 A/
25 ms
•
X
X
6EP1336-3BA10
20 A
60 A/
25 ms
•
X
X
6EP1436-2BA10
20 A
35 A/
100 ms
•
X
X
X
6EP3337-8SB00-0AY0
40 A
120 A/
25 ms
6EP1437-2BA20
40 A
65 A/
120 ms
•
•
X
6EP1437-3BA10
40 A
120 A/
25 ms
© Siemens AG 2016