Technical information and configuration
Installation guidelines, mouning areas and fixing options
■
Overview
Installation guidelines
SITOP und LOGO!Power power supplies are mostly built-in
devices. They must be mounted vertically so that the supply air
can enter the ventilation slots at the bottom of the devices and
leave through the upper part of the devices. The minimum clear-
ances specified in the relevant product documentation (operat-
ing instructions, device manuals) for the top and bottom of the
devices must be observed to ensure free air convection. Side
clearance is not required.
The option of mounting on standard mounting rails, wall mount-
ing or mounting in non-vertical positions with the appropriate
derating is specified in the respective device manuals.
Everything for project planning
Comprehensive information is available for mechanical and
electrical engineering, for example, 3D data, circuit diagram
macros, device manuals, product data sheets and certificates.
The information is available for download via the CAx Download
Manager.