SITOP DC UPS uninterruptible power supplies
DC UPS with battery modules
SITOP UPS1100 battery modules
Safety
Protection class
Class III
Class III
Class III
Class III
Class III
Class III
CE mark
Yes
Yes
Yes
Yes
Yes
Yes
UL/cUL (CSA)
approval
cURus-Recognized
(UL 1778, CSA C22.2
No. 107.1), File
E219627
cURus-Recognized
(UL 1778, CSA C22.2
No. 107.1), File
E219627
cURus-Recognized
(UL 1778, CSA C22.2
No. 107.1), File
E219627
cURus-Recognized
(UL 1778, CSA C22.2
No. 107.1), File
E219627
cURus-Recognized
(UL 1778, CSA C22.2
No. 107.1), File
E219627
cURus-Recognized
(UL 1778, CSA C22.2
No. 107.1), File
E219627
Explosion protection
IECEx Ex nA nC IIC
T4 Gc; cCSAus (CSA
C22.2 No. 213-
M1987, ANSI/ISA-
12.12.01-2013) Class
I, Div. 2, Group
ABCD, T4
IECEx Ex nA nC IIC
T4 Gc; cCSAus (CSA
C22.2 No. 213-
M1987, ANSI/ISA-
12.12.01-2013) Class
I, Div. 2, Group
ABCD, T4
IECEx Ex nA nC IIC
T4 Gc; cCSAus (CSA
C22.2 No. 213-
M1987, ANSI/ISA-
12.12.01-2013) Class
I, Div. 2, Group
ABCD, T4
No
IECEx Ex nA nC IIC
T4 Gc; cCSAus (CSA
C22.2 No. 213-
M1987, ANSI/ISA-
12.12.01-2013) Class
I, Div. 2, Group
ABCD, T4
IECEx Ex nA nC IIC
T4 Gc; cCSAus (CSA
C22.2 No. 213-
M1987, ANSI/ISA-
12.12.01-2013) Class
I, Div. 2, Group
ABCD, T4
Marine approval
GL, ABS
GL, ABS
GL, ABS
GL, ABS
GL, ABS
GL, ABS
Degree of protection
(EN 60529)
IP20
IP20
IP20
IP20
IP20
IP20
Operating data note
Operating data note
For storage,
mounting and
operation of lead-
acid batteries, the
relevant DIN/VDE
regulations or
country-specific
regulations (e.g.
VDE 0510 Part 2/
EN 50272-2) must be
observed. You must
ensure that the
battery site is suffi-
ciently ventilated.
Possible sources of
ignition must be at
least 50 cm away.
For storage,
mounting and
operation of lead-
acid batteries, the
relevant DIN/VDE
regulations or
country-specific
regulations (e.g.
VDE 0510 Part 2/
EN 50272-2) must be
observed. You must
ensure that the
battery site is suffi-
ciently ventilated.
Possible sources of
ignition must be at
least 50 cm away.
For storage,
mounting and
operation of lead-
acid batteries, the
relevant DIN/VDE
regulations or
country-specific
regulations (e.g.
VDE 0510 Part 2/
EN 50272-2) must be
observed. You must
ensure that the
battery site is suffi-
ciently ventilated.
Possible sources of
ignition must be at
least 50 cm away.
For storage,
mounting and
operation of
batteries, the relevant
DIN/VDE regulations
or country-specific
regulations (e.g.
VDE 0510 Part 2/
EN 50272-2) must be
observed.
For storage,
mounting and
operation of lead-
acid batteries, the
relevant DIN/VDE
regulations or
country-specific
regulations (e.g.
VDE 0510 Part 2/
EN 50272-2) must be
observed. You must
ensure that the
battery site is suffi-
ciently ventilated.
Possible sources of
ignition must be at
least 50 cm away.
For storage,
mounting and
operation of lead-
acid batteries, the
relevant DIN/VDE
regulations or
country-specific
regulations (e.g.
VDE 0510 Part 2/
EN 50272-2) must be
observed. You must
ensure that the
battery site is suffi-
ciently ventilated.
Possible sources of
ignition must be at
least 50 cm away.
Ambient temperature
• during operation
-15 ... 50 °C
-40 ... +60 °C
-15 ... 50 °C
-20 ... +50 °C
-15 ... 50 °C
-15 ... 50 °C
• during transport
-20 ... +50 °C
-40 ... +60 °C
-20 ... +50 °C
-40 ... +80 °C
-20 ... +50 °C
-20 ... +50 °C
• during storage
-20 ... +50 °C
-40 ... +60 °C
-20 ... +50 °C
-40 ... +35 °C
-20 ... +50 °C
-20 ... +50 °C
Relative temporary
capacity loss at 20 °C
in a month typical
3 %
3 %
3 %
3 %
3 %
3 %
Service life
Service life of energy
storage
• typical remark
capacity falls to 50 %
of original capacity
capacity falls to 50 %
of original capacity
capacity falls to 50 %
of original capacity
capacity falls to 50 %
of original capacity
capacity falls to 50 %
of original capacity
capacity falls to 50 %
of original capacity
• at 20 °C typical
4 years
10 years
4 years
15 years
4 years
4 years
• at 30 °C typical
2 years
7 years
2 years
10 years
2 years
2 years
• at 40 °C typical
1 year
3 years
1 year
9 years
1 year
1 years
• at 50 °C typical
0.5 years
1.5 years
0.5 years
2 years
0.5 years
0.5 years
• at 60 °C typical
-
1 year
-
-
-
-
Article number
6EP4131-0GB00-
0AY0
6EP4132-0GB00-
0AY0
6EP4133-0GB00-
0AY0
6EP4133-0JB00-
0AY0
6EP4134-0GB00-
0AY0
6EP4135-0GB00-
0AY0
Product
SITOP UPS1100
SITOP UPS1100
SITOP UPS1100
SITOP UPS1100
SITOP UPS1100
SITOP UPS1100
Product type
Lead battery
Pure-lead battery
Lead battery
LiFePo battery
Lead battery
Lead battery
Battery capacity
1.2 Ah
2.5 Ah
3.2 Ah
5 Ah
7 Ah
12 Ah
© Siemens AG 2016