SIEMENS
11/15
Siemens KT 10.1 · 2016
11
■
Technical specifications
(continued)
SITOP DC UPS uninterruptible power supplies
DC UPS with battery modules
SITOP UPS1600 DC UPS modules
Article number
6EP4134-3AB00-0AY0
6EP4136-3AB00-0AY0
6EP4137-3AB00-0AY0
6EP4134-3AB00-1AY0
6EP4136-3AB00-1AY0
6EP4137-3AB00-1AY0
6EP4134-3AB00-2AY0
6EP4136-3AB00-2AY0
6EP4137-3AB00-2AY0
Product brand name
SITOP UPS1600
SITOP UPS1600
SITOP UPS1600
Type of current supply
DC UPS 24 V/10 A
DC UPS 24 V/20 A
DC UPS 24 V/40 A
Input
Supply voltage at DC Rated value
24 V
24 V
24 V
Voltage curve at input
DC
DC
DC
input voltage range
22 ... 29 V DC
22 ... 29 V DC
22 ... 29 V DC
Adjustable response value voltage
for buffer connection preset
22.5 V
22.5 V
22.5 V
Adjustable response value voltage
for buffer connection
21 ... 25 V; Adjustable: 21 V, 21.5 V,
22 V, 22.5 V, 23 V, 24 V, 25 V DC
or via software
21 ... 25 V; Adjustable: 21 V, 21.5 V,
22 V, 22.5 V, 23 V, 24 V, 25 V DC
or via software
21 ... 25 V; Adjustable: 21 V, 21.5 V,
22 V, 22.5 V, 23 V, 24 V, 25 V DC
or via software
Input current at rated input voltage
24 V Rated value
14 A; for max. charging current (3 A)
25 A; for max. charging current (4 A)
46 A; for max. charging current (5 A)
Mains buffering
Type of energy storage
with batteries
with batteries
with batteries
Design of the mains power cut
bridging-connection
Adjustable range using rotary coding
switch: 0.5 min, 1 min, 2 min, 5 min,
10 min, 20 min, max. buffering time
or via software
Adjustable range using rotary coding
switch: 0.5 min, 1 min, 2 min, 5 min,
10 min, 20 min, max. buffering time
or via software
Adjustable range using rotary coding
switch: 0.5 min, 1 min, 2 min, 5 min,
10 min, 20 min, max. buffering time
or via software
Charging current
• 1
0.1 A
0.1 A
0.1 A
• 2
3 A
4 A
5 A
adjustable charging current maximum
Note
Automatically depending on battery
module
Automatically depending on battery
module
Automatically depending on battery
module
Output
Output voltage
• in normal operation at DC Rated
value
24 V
24 V
24 V
• in buffering mode at DC Rated value
24 V
24 V
24 V
Formula for output voltage
V
in
- approx. 0.01 x I
V
in
- approx. 0.01 x I
V
in
- approx. 0.01 x I
ON-delay time typical
60 s
60 s
60 s
Voltage increase time of the output
voltage typical
60 ms
60 ms
60 ms
Output voltage in buffering mode
at DC
19 ... 28.5 V
19 ... 28.5 V
19 ... 28.5 V
Output current
• Rated value
10 A
20 A
40 A
• in normal operation
0 ... 30 A
0 ... 60 A
0 ... 120 A
• in buffering mode
0 ... 30 A
0 ... 60 A
0 ... 120 A
Peak current
30 A
60 A
120 A
Property of the output Short-circuit
proof
Yes
Yes
Yes
Design of short-circuit protection
Limitation to 3 x
I
rated
for 30 ms/min;
through-conductivity for 1.5 x
I
rated
for 5 sec/min
Limitation to 3 x
I
rated
for 30 ms/min;
through-conductivity for 1.5 x
I
rated
for 5 sec/min
Limitation to 3 x
I
rated
for 30 ms/min;
through-conductivity for 1.5 x
I
rated
for 5 sec/min
Supplied active power typical
240 W
480 W
960 W
Efficiency
Efficiency in percent
• at rated output current at rated
output current typical
97.7 %
98.2 %
98.8 %
• in case of accumulator operation
typical
97.7 %
98.2 %
98.8 %
Power loss [W]
• at rated output current at rated
output current typical
5.6 W
8.6 W
12 W
• in case of accumulator operation
typical
5.6 W
8.6 W
12 W
© Siemens AG 2016