SIEMENS
2/10
Siemens KT 10.1 · 2016
2
■
Technical specifications
(continued)
SITOP compact
1-phase, 24 V DC
Efficiency
Efficiency at
V
out rated
, I
out rated
,
approx.
87 %
88 %
Power loss at
V
out rated
, I
out rated
,
approx.
14 W
13 W
Power loss [W] during no-load
operation maximum
0.75 W
0.75 W
Closed-loop control
Dynamic mains compensation
(
V
in rated
±15 %), max.
0.1 %
0.1 %
Dynamic load smoothing
(
I
out
: 10/90/10 %),
U
out
± typ.
3 %
3 %
Load step setting time 10 to 90%, typ.
4 ms
4 ms
Load step setting time 90 to 10%, typ.
4 ms
4 ms
Protection and monitoring
Output overvoltage protection
Yes, according to EN 60950-1
Yes, according to EN 60950-1
Current limitation, typ.
4 A
4.8 A
Property of the output Short-circuit
proof
Yes
Yes
Short-circuit protection
Electronic shutdown, automatic restart
Electronic shutdown, automatic restart
Overload/short-circuit indicator
-
-
Safety
Primary/secondary isolation
Yes
Yes
Galvanic isolation
Safety extra-low output voltage
U
out
acc. to EN 60950-1
and EN 50178
Safety extra-low output voltage
U
out
acc. to EN 60950-1
and EN 50178
Protection class
Class I
Class I
Leakage current
• maximum
3.5 mA
3.5 mA
• typical
0.4 mA
0.4 mA
CE mark
Yes
Yes
UL/cUL (CSA) approval
cULus-Listed (UL 508, CSA C22.2 No. 107.1),
File E197259; cURus-Recognized (UL 60950,
CSA C22.2 No. 60950), File E151273, NEC class 2
(acc. to UL 1310)
cULus-Listed (UL 508, CSA C22.2 No. 107.1),
File E197259; cCSAus (CSA C22.2 No. 60950-1,
UL 60950-1)
Explosion protection
ATEX (EX) II 3G Ex nA IIC T4; cCSAus
(CSA C22.2 No. 213-M1987, ANSI/ISA-12.12.01-2007)
Class I, Div. 2, Group ABCD, T4
ATEX (EX) II 3G Ex nA IIC T4; cCSAus
(CSA C22.2 No. 213-M1987, ANSI/ISA-12.12.01-2007)
Class I, Div. 2, Group ABCD, T4
FM approval
-
-
CB approval
Yes
Yes
Marine approval
GL, ABS
GL, ABS
Degree of protection (EN 60529)
IP20
IP20
Article number
6EP1332-5BA20
6EP1332-5BA10
Product
SITOP PSU100C
SITOP PSU100C
Power supply, type
24 V/3.7 A
24 V/4 A
© Siemens AG 2016