SIEMENS
2/9
Siemens KT 10.1 · 2016
2
■
Technical specifications
(continued)
SITOP compact
1-phase, 24 V DC
Article number
6EP1332-5BA20
6EP1332-5BA10
Product
SITOP PSU100C
SITOP PSU100C
Power supply, type
24 V/3.7 A
24 V/4 A
Input
Input
1-phase AC or DC
1-phase AC or DC
Rated voltage value
V
in rated
100 ... 230 V
100 ... 230 V
Voltage range AC
85 ... 264 V
85 ... 264 V
Input voltage
• at DC
110 ... 300 V
110 ... 300 V
Wide-range input
Yes
Yes
Overvoltage resistance
2.3 ×
V
in rated
, 1.3 ms
2.3 ×
V
in rated
, 1.3 ms
Mains buffering at
I
out rated
, min.
20 ms; at
V
in
= 230 V
20 ms; at
V
in
= 230 V
Rated line frequency 1
50 Hz
50 Hz
Rated line frequency 2
60 Hz
60 Hz
Rated line range
47 ... 63 Hz
47 ... 63 Hz
Input current
• at rated input voltage 100 V
1.88 A
2.25 A
• at rated input voltage 230 V
0.95 A
1.15 A
Switch-on current limiting (+25 °C),
max.
30 A
34 A
I²t, max.
3 A²·s
3 A²·s
Built-in incoming fuse
internal
internal
Protection in the mains power input
(IEC 898)
Recommended miniature circuit breaker:
from 16 A characteristic B or
from 10 A characteristic C
Recommended miniature circuit breaker:
from 16 A characteristic B or
from 10 A characteristic C
Output
Output
Controlled, isolated DC voltage
Controlled, isolated DC voltage
Rated voltage
V
out
DC
24 V
24 V
Total tolerance, static ±
3 %
3 %
Static mains compensation, approx.
0.1 %
0.1 %
Static load balancing, approx.
0.2 %
0.2 %
Residual ripple peak-peak, max.
200 mV
200 mV
Residual ripple peak-peak, typ.
90 mV
80 mV
Spikes peak-peak, max.
(bandwidth: 20 MHz)
300 mV
300 mV
Spikes peak-peak, typ.
(bandwidth: 20 MHz)
60 mV
80 mV
Adjustment range
22.2 ... 26.4 V
Product function Output voltage
adjustable
No
Yes
Output voltage setting
-
via potentiometer
Status display
Green LED for output voltage OK
Green LED for output voltage OK
On/off behavior
Overshoot of
V
out
approx. 1 %
Overshoot of
V
out
approx. 1 %
Startup delay, max.
1.5 s
1.5 s
Voltage rise, typ.
500 ms
400 ms
Rated current value
I
out rated
3.7 A
4 A
Current range
0 ... 3.7 A
0 ... 4 A
• Note
+55 ... +70 °C: Derating 3,5%/K
+55 ... +70 °C: Derating 3,5%/K
Supplied active power typical
89 W
96 W
Short-term overload current
• at short-circuit during operation
typical
-
-
Parallel switching for enhanced
performance
No
Yes; Start-up with single nominal load only
Numbers of parallel switchable units
for enhanced performance
-
2
© Siemens AG 2016