SIEMENS
10/7
Siemens KT 10.1 · 2016
10
Add-on modules
Selectivity module
■
Technical specifications
Article number
6EP1961-2BA11
6EP1961-2BA31
6EP1961-2BA21
6EP1961-2BA41
6EP1961-2BA00
Product brand name
SITOP PSE200U
SITOP PSE200U
SITOP PSE200U
SITOP PSE200U
SITOP select
Type of current supply
Selectivity module,
4 x 3 A Common
signal contact
Selectivity module,
4 x 3 A Single-
channel signaling
Selectivity module,
4 x 10 A Common
signal contact
Selectivity module,
4 x 10 A Single-
channel signaling
Diagnosis module,
4 x 10 A
Input
Input
Controlled DC voltage
Controlled DC voltage
Controlled DC voltage
Controlled DC voltage
Controlled DC voltage
(SITOP select is not
designed for operation
with DC UPS module
40 A (6EP1 931-2FC21/
-2FC42)
Supply voltage at DC Rated value
24 V
24 V
24 V
24 V
24 V
Input voltage at DC
22 ... 30 V
22 ... 30 V
22 ... 30 V
22 ... 30 V
22 ... 30 V
Overvoltage resistance
35 V
35 V
35 V
35 V
35 V; 100 ms
Input current
12 A
12 A
40 A
40 A
40 A
Output
Output
controlled DC voltage
controlled DC voltage
controlled DC voltage
controlled DC voltage
controlled DC voltage
Output voltage
V
in
- approx. 0.2 V
V
in
- approx. 0.2 V
V
in
- approx. 0.2 V
V
in
- approx. 0.2 V
V
in
- approx. 0.3 V
Overall tolerance
In accordance with the
supplying input
voltage
In accordance with the
supplying input
voltage
In accordance with the
supplying input
voltage
In accordance with the
supplying input
voltage
In accordance with the
supplying input
voltage
Number of outputs
4
4
4
4
4
Output current up to 60 °C per output
3 A
3 A
10 A
10 A
10 A
Adjustable pick-up value current of
the current-dependent overload
release
0.5 ... 3 A
0.5 ... 3 A
3 ... 10 A
3 ... 10 A
2 ... 10 A
Type of response value setting
via potentiometer
via potentiometer
via potentiometer
via potentiometer
via potentiometer
Product feature parallel switching of
outputs
No
No
No
No
No
Product feature bridging of
equipments
Yes
Yes
Yes
Yes
Yes
Type of outputs connection
Simultaneous
connection of all
outputs after power up
of the supply voltage
> 20 V, delay time of
25 ms, 100 ms or
adjustable "load
optimised" via DIP
switch for sequential
connection
Simultaneous
connection of all
outputs after power up
of the supply voltage
> 20 V, delay time of
25 ms, 100 ms or
adjustable "load
optimised" via DIP
switch for sequential
connection
Simultaneous
connection of all
outputs after power up
of the supply voltage
> 20 V, delay time of
25 ms, 100 ms or
adjustable "load
optimised" via DIP
switch for sequential
connection
Simultaneous
connection of all
outputs after power up
of the supply voltage
> 20 V, delay time of
25 ms, 100 ms or
adjustable "load
optimised" via DIP
switch for sequential
connection
Simultaneous
connection of all
outputs after power up
of the supply voltage,
delay time of 24 ms or
100 ms program-
mable for sequential
connection
Efficiency
Efficiency in percent
97 %
97 %
99 %
99 %
97 %
Power loss at rated output current
typical
9 W
9 W
10 W
10 W
30 W
Switch-off characteristic per output
Switching characteristic
• of the excess current
I
out
= 1.0 ...1.5 x set
value, switch-off after
approx. 5 s
I
out
= 1.0 ...1.5 x set
value, switch-off after
approx. 5 s
I
out
= 1.0 ...1.5 x set
value, switch-off after
approx. 5 s
I
out
= 1.0 ...1.5 x set
value, switch-off after
approx. 5 s
I
out
= 1.0 ...1.3 x set
value, switch-off after
approx. 5 s
• of the current limitation
I
out
= 1.5 x set value,
switch-off not before
typ. 100 ms
I
out
= 1.5 x set value,
switch-off not before
typ. 100 ms
I
out
= 1.5 x set value,
switch-off not before
typ. 100 ms
I
out
= 1.5 x set value,
switch-off not before
typ. 100 ms
I
out
= 1.3 x set value,
switch-off after approx.
50 ... 100 ms
• of the immediate switch-off
I
out
> set value and
V
in
< 20 V, switch-off
after approx. 0.5 ms
I
out
> set value and
V
in
< 20 V, switch-off
after approx. 0.5 ms
I
out
> set value and
V
in
< 20 V, switch-off
after approx. 0.5 ms
I
out
> set value and
V
in
< 20 V, switch-off
after approx. 0.5 ms
I
out
> set value and
V
in
< 20 V, switch-off
after approx. 0.5 ms
Residual current at switch-off typical
20 mA
Design of the reset device/resetting
mechanism
via sensor per output
via sensor per output
via sensor per output
via sensor per output
Using keys on the
module
Remote reset
Non-electrically
isolated 24 V input
(signal level "high" at >
15 V)
Non-electrically
isolated 24 V input
(signal level "high" at >
15 V)
Non-electrically
isolated 24 V input
(signal level "high" at >
15 V)
Non-electrically
isolated 24 V input
(signal level "high" at >
15 V)
-
© Siemens AG 2016