SIEMENS
9/34
Siemens KT 10.1 · 2016
9
■
Technical specifications
(continued)
Special designs, special uses
Special applications
1-phase, 24 V DC
Output
Output
Controlled, isolated DC voltage
Controlled, isolated DC voltage
Rated voltage
V
out
DC
24 V
24 V
Total tolerance, static ±
1 %
1 %
Static mains compensation, approx.
0.1 %
0.1 %
Static load balancing, approx.
0.5 %
0.5 %
Residual ripple peak-peak, max.
150 mV
150 mV
Residual ripple peak-peak, typ.
40 mV
50 mV
Spikes peak-peak, max. (bandwidth: 20 MHz)
240 mV
240 mV
Spikes peak-peak, typ. (bandwidth: 20 MHz)
100 mV
200 mV
Adjustment range
22 ... 29 V
22 ... 29 V
Product function Output voltage adjustable
Yes
Yes
Output voltage setting
via potentiometer
via potentiometer
Status display
Green LED for 24 V OK
Green LED for 24 V OK
On/off behavior
No overshoot of
V
out
(soft start)
No overshoot of
V
out
(soft start)
Startup delay, max.
2 s
2 s
Voltage rise, typ.
40 ms
40 ms
Rated current value
I
out rated
5 A
10 A
Current range
0 ... 5 A
0 ... 10 A
Supplied active power typical
120 W
240 W
Short-term overload current
• on short-circuiting during the start-up typical
20 A
35 A
• at short-circuit during operation typical
20 A
35 A
Duration of overloading capability for excess
current
• on short-circuiting during the start-up
500 ms
700 ms
• at short-circuit during operation
500 ms
700 ms
Parallel switching for enhanced performance
Yes
Yes
Numbers of parallel switchable units for
enhanced performance
2
2
Efficiency
Efficiency at
V
out rated
, I
out rated
, approx.
88 %
89 %
Power loss at
V
out rated
, I
out rated
, approx.
17 W
30 W
Closed-loop control
Dynamic mains compensation
(
V
in rated
±15 %), max.
0.3 %
0.3 %
Dynamic load smoothing
(
I
out
: 50/100/50 %),
U
out
± typ.
0.5 %
0.6 %
Load step setting time 50 to 100%, typ.
0.1 ms
0.1 ms
Load step setting time 100 to 50%, typ.
0.1 ms
0.2 ms
Protection and monitoring
Output overvoltage protection
Additional control loop, shutdown at approx. 33 V,
automatic restart
Additional control loop, shutdown at approx. 33 V,
automatic restart
Current limitation
5.5 ... 6.5 A
11 ... 13 A
Property of the output Short-circuit proof
Yes
Yes
Short-circuit protection
Electronic shutdown, automatic restart
Electronic shutdown, automatic restart
Enduring short circuit current RMS value
• maximum
5 A
10 A
Overload/short-circuit indicator
-
-
Safety
Primary/secondary isolation
Yes
Yes
Galvanic isolation
Safety extra-low output voltage
U
out
acc. to
EN 60950-1 and EN 50178
Safety extra-low output voltage
U
out
acc. to
EN 60950-1 and EN 50178
Protection class
Class I
Class I
Leakage current
• maximum
3.5 mA
3.5 mA
• typical
0.26 mA
0.27 mA
CE mark
Yes
Yes
UL/cUL (CSA) approval
cULus-Listed (UL 508, CSA C22.2 No. 107.1),
File E197259
cULus-Listed (UL 508, CSA C22.2 No. 107.1),
File E197259
Article number
6EP1333-1AL12
6EP1334-1AL12
Product
SITOP power
SITOP power
Power supply, type
24 V/5 A
24 V/10 A
© Siemens AG 2016