Technical specifications
(continued)
SITOP compact
1-phase, 24 V DC
Output
Output
Controlled, isolated DC voltage
Controlled, isolated DC voltage
Controlled, isolated DC voltage
Rated voltage
V
out
DC
24 V
24 V
24 V
Total tolerance, static ±
3 %
3 %
3 %
Static mains compensation, approx.
0.1 %
0.1 %
0.1 %
Static load balancing, approx.
0.2 %
0.2 %
0.2 %
Residual ripple peak-peak, max.
200 mV
200 mV
200 mV
Residual ripple peak-peak, typ.
40 mV
25 mV
55 mV
Spikes peak-peak, max.
(bandwidth: 20 MHz)
300 mV
300 mV
300 mV
Spikes peak-peak, typ.
(bandwidth: 20 MHz)
20 mV
20 mV
50 mV
Adjustment range
-
22.2 ... 26.4 V
22.2 ... 26.4 V
Product function Output voltage
adjustable
No
Yes
Yes
Output voltage setting
-
via potentiometer
via potentiometer
Status display
Green LED for output voltage OK
Green LED for output voltage OK
Green LED for output voltage OK
On/off behavior
Overshoot of
V
out
approx. 5 %
Overshoot of
V
out
approx. 5 %
Overshoot of
V
out
approx. 1 %
Startup delay, max.
1 s
0.6 s
0.7 s
Voltage rise, typ.
25 ms
90 ms
100 ms
Rated current value
I
out rated
0.6 A
1.3 A
2.5 A
Current range
0 ... 0.6 A
0 ... 1.3 A
0 ... 2.5 A
• Note
+55 ... +70 °C: Derating 3%/K
+55 ... +70 °C: Derating 3%/K
+55 ... +70 °C: Derating 3,5%/K
Supplied active power typical
14 W
30 W
60 W
Short-term overload current
• at short-circuit during operation
typical
1 A
3.1 A
-
Parallel switching for enhanced
performance
No
Yes; Start-up with single nominal load
only
Yes; Start-up with single nominal load
only
Numbers of parallel switchable units
for enhanced performance
-
2
2
Efficiency
Efficiency at
V
out rated
, I
out rated
,
approx.
82 %
86 %
87 %
Power loss at
V
out rated
, I
out rated
,
approx.
2.6 W
4.5 W
9 W
Power loss [W] during no-load
operation maximum
0.75 W
0.75 W
0.75 W
Closed-loop control
Dynamic mains compensation
(
V
in rated
±15 %), max.
0.1 %
0.1 %
0.1 %
Dynamic load smoothing
(
I
out
: 10/90/10 %),
U
out
± typ.
3 %
3 %
3 %
Load step setting time 10 to 90%, typ.
3 ms
5 ms
4 ms
Load step setting time 90 to 10%, typ.
3 ms
5 ms
4 ms
Protection and monitoring
Output overvoltage protection
Yes, according to EN 60950-1
Yes, according to EN 60950-1
Yes, according to EN 60950-1
Current limitation, typ.
0.7 A
1.4 A
3 A
Property of the output Short-circuit
proof
Yes
Yes
Yes
Short-circuit protection
Electronic shutdown, automatic restart
Electronic shutdown, automatic restart
Electronic shutdown, automatic restart
Overload/short-circuit indicator
-
-
-
Article number
6EP1331-5BA00
6EP1331-5BA10
6EP1332-5BA00
Product
SITOP PSU100C
SITOP PSU100C
SITOP PSU100C
Power supply, type
24 V/0.6 A
24 V/1.3 A
24 V/2.5 A
© Siemens AG 2016