SIEMENS
9/7
Siemens KT 10.1 · 2016
9
Special designs, special uses
Wall mounting
1-phase, 24 V DC
(PSU100D)
■
Overview
The single-phase PSU100Ds are switch mode power supplies
for direct wall mounting using screws. The flat and rugged alu-
minum enclosure with IP20 degree of protection can be installed
in various orientations and is therefore ideal for installation loca-
tions with limited space or for mounting in control cabinets and
enclosures without a DIN rail. The low-cost devices meet all the
basic requirements for a power supply, typical applications be-
ing apparatus, automated equipment and automation solutions.
Main product highlights
•
24 V DC/ 2.1 A and 3.1 A, 4.1 A, 6.2 A and 12.5 A
•
Compact metal enclosure
•
Wide-range input
•
Green LED for "24 V OK"
•
Certification in accordance with CE and UL
•
Adjustable output voltage from 22 to 28 V or from 11 to 14 V
for compensating voltage drops
•
Temperature range from -10 °C to +70 °C
■
Technical specifications
Article number
6EP1331-1LD00
6EP1332-1LD00
6EP1332-1LD10
6EP1333-1LD00
6EP1334-1LD00
Product
PSU100D
PSU100D
PSU100D
PSU100D
PSU100D
Power supply, type
24 V/2.1 A
24 V/3.1 A
24 V/4.1 A
24 V/6.2 A
24 V/12.5 A
Input
Input
1-phase AC
1-phase AC
1-phase AC
1-phase AC
1-phase AC
Rated voltage value
V
in rated
100 ... 240 V
100 ... 240 V
100 ... 240 V
100 ... 240 V
100 ... 240 V
Voltage range AC
85 ... 264 V
85 ... 264 V
85 ... 264 V
85 ... 264 V
85 ... 264 V
Wide-range input
Yes
Yes
Yes
Yes
Yes
Mains buffering at
I
out rated
, min.
15 ms;
at
V
in
= 115/230 V
15 ms;
at
V
in
= 115/230 V
15 ms;
at
V
in
= 115/230 V
15 ms;
at
V
in
= 115/230 V
15 ms;
at
V
in
= 115/230 V
Rated line frequency 1
50 Hz
50 Hz
50 Hz
50 Hz
50 Hz
Rated line frequency 2
60 Hz
60 Hz
60 Hz
60 Hz
60 Hz
Rated line range
47 ... 63 Hz
47 ... 63 Hz
47 ... 63 Hz
47 ... 63 Hz
47 ... 63 Hz
Input current
• at rated input voltage 100 V
1.1 A
1.5 A
2 A
3.1 A
4 A
• at rated input voltage 240 V
0.7 A
1 A
1.1 A
2 A
2 A
Switch-on current limiting
(+25 °C), max.
60 A
60 A
75 A
75 A
60 A
I²t, max.
1.2 A²·s
1.2 A²·s
4 A²·s
6.5 A²·s
1.1 A²·s
Built-in incoming fuse
internal
internal
internal
internal
internal
Protection in the mains power input
(IEC 898)
Recommended
miniature circuit
breaker: from 10 A
characteristic C or
from 16 A
characteristic B
Recommended
miniature circuit
breaker: from 10 A
characteristic C or
from 16 A
characteristic B
Recommended
miniature circuit
breaker: from 10 A
characteristic C or
from 16 A
characteristic B
Recommended
miniature circuit
breaker: from 10 A
characteristic C or
from 16 A
characteristic B
Recommended
miniature circuit
breaker: from 10 A
characteristic C or
from 16 A
characteristic B
© Siemens AG 2016