Technical specifications
(continued)
SITOP compact
1-phase, 12 V DC
Output
Output
Controlled, isolated DC voltage
Controlled, isolated DC voltage
Rated voltage
V
out
DC
12 V
12 V
Total tolerance, static ±
3 %
3 %
Static mains compensation, approx.
0.5 %
0.5 %
Static load balancing, approx.
1 %
1 %
Residual ripple peak-peak, max.
200 mV
200 mV
Residual ripple peak-peak, typ.
40 mV
80 mV
Spikes peak-peak, max. (bandwidth: 20 MHz)
300 mV
300 mV
Spikes peak-peak, typ. (bandwidth: 20 MHz)
50 mV
80 mV
Adjustment range
10.5 ... 12.9 V
10.5 ... 12.9 V
Product function Output voltage adjustable
Yes
Yes
Output voltage setting
via potentiometer
via potentiometer
Status display
Green LED for output voltage OK
Green LED for output voltage OK
On/off behavior
Overshoot of
V
out
approx. 5 %
Overshoot of
V
out
approx. 1 %
Startup delay, max.
0.6 s
1 s
Voltage rise, typ.
10 ms
500 ms
Rated current value
I
out
rated
2 A
6.5 A
Current range
0 ... 2 A
0 ... 6.5 A
• Note
+55 ... +70 °C: Derating 3%/K
+50 ... +70 °C: Derating 3.5%/K
Supplied active power typical
24 W
78 W
Parallel switching for enhanced performance
Yes; Start-up with single nominal load only
Yes; Start-up with single nominal load only
Numbers of parallel switchable units for
enhanced performance
2
2
Efficiency
Efficiency at
V
out rated
, I
out rated
, approx.
82 %
86 %
Power loss at
V
out rated
, I
out rated
, approx.
5.8 W
12.5 W
Power loss [W] during no-load operation
maximum
0.75 W
0.75 W
Closed-loop control
Dynamic mains compensation
(
V
in
rated
±15 %), max.
0.1 %
0.1 %
Dynamic load smoothing (
V
out
: 10/90/10 %),
U
out
± typ.
3 %
3 %
Load step setting time 10 to 90%, typ.
4 ms
3 ms
Load step setting time 90 to 10%, typ.
3 ms
3 ms
Protection and monitoring
Output overvoltage protection
Yes, according to EN 60950-1
Yes, according to EN 60950-1
Current limitation, typ.
2.4 A
7.2 A
Property of the output Short-circuit proof
Yes
Yes
Short-circuit protection
Electronic shutdown, automatic restart
Electronic shutdown, automatic restart
Overload/short-circuit indicator
-
-
Safety
Primary/secondary isolation
Yes
Yes
Galvanic isolation
Safety extra-low output voltage
U
out
acc. to
EN 60950-1 and EN 50178
Safety extra-low output voltage
U
out
acc. to
EN 60950-1 and EN 50178
Protection class
Class I
Class I
Leakage current
• maximum
3.5 mA
3.5 mA
• typical
0.4 mA
0.4 mA
CE mark
Yes
Yes
UL/cUL (CSA) approval
cULus-Listed (UL 508, CSA C22.2 No. 107.1),
File E197259; cCSAus (CSA C22.2 No. 60950-1,
UL 60950-1)
cULus-Listed (UL 508, CSA C22.2 No. 107.1),
File E197259; cCSAus (CSA C22.2 No. 60950-1,
UL 60950-1)
Explosion protection
ATEX (EX) II 3G Ex nA IIC T4; cCSAus (CSA C22.2
No. 213-M1987, ANSI/ISA-12.12.01-2007) Class I,
Div. 2, Group ABCD, T4
ATEX (EX) II 3G Ex nA IIC T4; cCSAus (CSA C22.2
No. 213-M1987, ANSI/ISA-12.12.01-2007) Class I,
Div. 2, Group ABCD, T4
FM approval
-
-
CB approval
Yes
Yes
Marine approval
GL, ABS
GL, ABS
Degree of protection (EN 60529)
IP20
IP20
Article number
6EP1321-5BA00
6EP1322-5BA10
Product
SITOP PSU100C
SITOP PSU100C
Power supply, type
12 V/2 A
12 V/6.5 A