SIEMENS
8/12
Siemens KT 10.1 · 2016
8
■
Technical specifications
(continued)
SITOP in the SIMATIC Design
1-phase, 24 V DC (for S7-1500 and ET200MP)
Output
Output
Controlled, isolated DC voltage
Controlled, isolated DC voltage
Rated voltage
V
out
DC
24 V
24 V
Total tolerance, static ±
1 %
1 %
Static mains compensation, approx.
0.1 %
0.1 %
Static load balancing, approx.
0.1 %
0.1 %
Residual ripple peak-peak, max.
50 mV
50 mV
Spikes peak-peak, max.
(bandwidth: 20 MHz)
150 mV
150 mV
Product function
Output voltage adjustable
No
No
Status display
LED green for 24 V OK; LED red for error;
LED yellow for stand-by
LED green for 24 V OK; LED red for error;
LED yellow for stand-by
On/off behavior
No overshoot of
V
out
(soft start)
No overshoot of
V
out
(soft start)
Startup delay, max.
1.5 s
1.5 s
Voltage rise, typ.
10 ms
10 ms
Rated current value
I
out rated
3 A
8 A
Current range
0 ... 3 A
0 ... 8 A
Supplied active power typical
72 W
192 W
Short-term overload current
• on short-circuiting during the
start-up typical
12 A
35 A
• at short-circuit during operation
typical
12 A
35 A
Duration of overloading capability for
excess current
• on short-circuiting during the
start-up
70 ms
70 ms
• at short-circuit during operation
70 ms
70 ms
Parallel switching for enhanced
performance
No
No
Efficiency
Efficiency at
V
out rated
,
I
out rated
,
approx.
87 %
90 %
Power loss at
V
out rated
,
I
out rated
,
approx.
11 W
21 W
Closed-loop control
Dynamic mains compensation
(
V
in rated
±15 %), max.
0.1 %
0.1 %
Dynamic load smoothing
(
I
out
: 50/100/50 %),
U
out
± typ.
1 %
2 %
Dynamic load smoothing
(
I
out
: 10/90/10 %),
U
out
± typ.
3 %
3 %
Load step setting time 10 to 90%, typ.
5 ms
5 ms
Load step setting time 90 to 10%, typ.
5 ms
5 ms
Setting time maximum
5 ms
5 ms
Protection and monitoring
Output overvoltage protection
Additional control loop, limitation (closed loop control)
at < 28.8 V
Additional control loop, limitation (closed loop control)
at < 28.8 V
Current limitation
3.15 ... 3.6 A
8.4 ... 9.6 A
Current limitation, typ.
3.4 A
9 A
Property of the output
Short-circuit proof
Yes
Yes
Short-circuit protection
Electronic shutdown, automatic restart
Electronic shutdown, automatic restart
Overload/short-circuit indicator
-
-
Article number
6EP1332-4BA00
6EP1333-4BA00
Product
S7-1500 PM1507
S7-1500 PM1507
Power supply, type
24 V/3 A
24 V/8 A