SIEMENS
5/86
Siemens NC 62 · 2016
5
SINAMICS S120 drive system
Blocksize format – Power Modules
Power Modules
■
Technical specifications
Article No.
6SL3210-...
Product designation
Power Modules in blocksize format
Line voltage
Up to 2000 m (6562 ft)
above sea level
200 … 240 V ±10 % 1 AC
(-15 % < 1 min) or
380 ... 480 V 3 AC ±10 %
(-15 % < 1 min)
Line frequency
47 … 63 Hz
Line power factor
At rated power
• Fundamental (cos
ϕ
1
)
> 0.96
• Total (
λ
)
-
200 … 240 V 1 AC
0.45 … 0.7
- 380 … 480 V 3 AC
0.65 … 0.95
Overvoltage category
According to EN 60664-1
Class III
Precharging frequency
Of the DC link, max.
1× every 30 s
DC link voltage, approx.
1.35 × line voltage
Output frequency
0 … 650 Hz
1)2)
Electronics power supply
24 V DC -15 %/+20 %
Radio interference suppression
• Standard
No radio interference suppression
• With integrated line filter
Category C2 to EN 61800-3
Cooling method
Increased air cooling by means of
built-in fan
Ambient or coolant
temperature (air)
In operation for line-side
components, Power Modules
0 ... 40 °C (32 ... 104 °F)
without derating,
> 40 … 55 °C (> 104 ... 131 °F)
see derating characteristics
Installation altitude
Up to 1000 m (3281 ft)
above sea level without derating,
>1000 ... 4000 m
(3281 ... 13124 ft)
above sea level
see derating characteristics
Declarations of conformity
CE (Low Voltage and
EMC Directives)
Certificate of suitability
cULus
Safety Integrated
Safety Integrity Level 2 (SIL 2)
acc. to IEC 61508,
Performance Level d (PLd)
acc. to ISO 13849-1
and Control Category 3
acc. to ISO 13849-1 or EN 954-1
1)
Note the correlation between max. output frequency, pulse frequency and
current derating. For further information see System Description.
2)
The output frequency is currently limited to 550 Hz. The specified values
apply to systems with license for high output frequency. Fore more informa-
tion, refer to section Control Units and
© Siemens AG 2016