> Line filters
■
Overview
Line filter
In plants with strict EMC requirements, line filters work together
with line reactors to restrict the conducted interference emanat-
ing from the Power Modules to the limit values of Class A1 as de-
fined in EN 55011 and Category C2 as defined in EN 61800-3.
Line filters are suitable only for direct connection to TN systems.
The use of other makes of line filter can lead to malfunctions or
irreparable damage to equipment.
■
Selection and ordering data
■
Technical specifications
Suitable for
Basic Line Module
SINAMICS line filter
Rated
power
Basic
Line
Module
Booksize format
Rated
current
kW (HP)
Type
A
Article No.
20 (25)
6SL3130-1TE22-0AA0
36
6SL3000-0BE21-6DA0
40 (50)
6SL3130-1TE24-0AA0
74
6SL3000-0BE23-6DA1
100 (125)
6SL3130-1TE31-0AA0
192
6SL3000-0BE31-2DA0
Article No.
6SL3000-0BE21-6DA0
6SL3000-0BE23-6DA1
6SL3000-0BE31-2DA0
Product designation
Line filter
Line filter
Line filter
Line voltage 380 … 480 V 3 AC
Rated current
A
36
74
192
Power loss
W
16
20
90
Line/load connection
L1, L2, L3/U, V, W
Screw-type terminals
Screw-type terminals
Screw-type terminals
• Conductor cross-section
mm
2
10
35
95
PE connection
M6 screw stud
M6 screw stud
M10 screw stud
Degree of protection
IP20
IP20
IP20
Width
mm (in)
50 (1.97)
75 (2.95)
150 (5.91)
Height
mm (in)
429 (16.89)
433 (17.05)
479 (18.86)
Depth
mm (in)
226 (8.90)
226 (8.90)
226 (8.90)
Net weight
kg (lb)
5 (11)
7.5 (16.5)
18.8 (41.5)
Certificate of suitability
cURus
cURus
cURus