SIEMENS
5/52
Siemens NC 62 · 2016
5
SINAMICS S120 drive system
Booksize format – Line Modules
Basic Line Modules
> Line reactors
■
Overview
20 kW and 100 kW line reactors
Line reactors reduce low-frequency line harmonic distortions
and offload the semiconductors of the Basic Line Module.
The use of other makes of line reactor can lead to malfunctions
or irreparable damage to equipment.
■
Selection and ordering data
■
Technical specifications
Suitable for
Basic Line Module
SINAMICS line reactor
Rated
power
Basic
Line
Module
Booksize format
Rated
current
kW (HP)
Type
A
Article No.
20 (25)
6SL3130-1TE22-0AA0
37
6SL3000-0CE22-0AA0
40 (50)
6SL3130-1TE24-0AA0
74
6SL3000-0CE24-0AA0
100 (125)
6SL3130-1TE31-0AA0
185
6SL3000-0CE31-0AA0
Article No.
6SL3000-0CE22-0AA0
6SL3000-0CE24-0AA0
6SL3000-0CE31-0AA0
Product designation
Line reactor
Line reactor
Line reactor
Line voltage 380 … 480 V 3 AC
Rated current
A
37
74
185
Power loss
• At 50 Hz
W
130
270
480
• At 60 Hz
W
154
320
565
Line/load connection
Screw-type terminals
Screw-type terminals
Flat connector for M8 screw
• Conductor cross-section
mm
2
0.5 … 16
2.5 … 35
–
Degree of protection
IP20
IP20
IP00
Width
mm (in)
178 (7.01)
210 (8.27)
261 (10.28)
Height
mm (in)
165 (6.50)
245 (9.65)
228 (8.98)
Depth
mm (in)
100 (3.94)
93 (3.66)
137 (5.39)
Net weight
kg (lb)
5.2 (11.5)
11.2 (24.7)
21.7 (47.8)
Certificate of suitability
cURus
cURus
cURus
© Siemens AG 2016