SIEMENS
4/10
Siemens NC 82 · 2017
SINAMICS S120 drive system
SINAMICS S120 Combi
Power Modules
> Line filters
4
■
Overview
Line filter
In plants with strict EMC requirements, line filters work together
with line reactors to restrict the conducted interference emanat-
ing from the Power Modules to the limit values of Class A1 as de-
fined in EN 55011 and Category C2 as defined in EN 61800-3.
Line filters are suitable only for direct connection to TN systems.
The use of other makes of line filter can lead to malfunctions or
irreparable damage to equipment.
Note:
According to product standard IEC 61800-3, RFI suppression
commensurate with the relevant rated conditions must be
provided and is a legal requirement in the EU (EMC Directive).
Line filters and line reactors are required for this purpose.
The machine manufacturer must provide verification that the
machinery to be operated with the drive products and the
installed suppression elements, e.g. line filters, are CE-EMC-
compliant.
■
Technical specifications
■
Selection and ordering data
Article No.
6SL3000-0BE21-6DA0
Product brand name
SINAMICS
Product designation
Line filter
Rated current
36 A
Rated infeed power
10 kW
16 kW
20 kW
Power loss in rated operation
12 W
15 W
16 W
Line/load connection
L1, L2, L3/U, V, W
Screw-type terminals
• Conductor cross-section
10 mm
2
PE connection
M6 screw stud
Degree of protection
IP20
Width
50 mm
Height
429 mm
Depth
226 mm
Net weight
5 kg
Certificate of suitability
cURus
Suitable for SINAMICS S120 Combi
SINAMICS
line filter
Rated
power
Infeed
Power Module
kW
Type
Article No.
16
16
20
6SL3111-3VE21-6FA0
6SL3111-3VE21-6EA0
6SL3111-3VE22-0HA0
6SL3000-0BE21-6DA0
10
16
16
20
6SL3111-4VE21-0EA0
6SL3111-4VE21-6FA0
6SL3111-4VE21-6EA0
6SL3111-4VE22-0HA0
© Siemens AG 2016