SIEMENS
4/44
Siemens NC 82 · 2017
SINAMICS S120 drive system
SINAMICS S120 in booksize format
Motor Modules
> Double Motor Modules
4
■
Technical specifications
(continued)
Article No.
–
–
–
6SL3120-2TE21-8AC0
Product designation
Double Motor Module in booksize format internal
air cooling C type
Article No.
6SL3120-2TE13-0AD0
6SL3120-2TE15-0AD0
6SL3120-2TE21-0AD0
6SL3120-2TE21-8AD0
Product designation
Double Motor Module in booksize format internal
air cooling D type
Product brand name
SINAMICS
Product type designation
S120
DC link voltage 510 ... 720 V DC
Output current
• Rated current
I
rated
A
2 × 3
2 × 5
2 × 9
2 × 18
•
I
S6
(40 %)
-
C type
A
–
–
–
2 × 24
-
D type
A
2 × 4
2 × 6.7
2 × 12
2 × 24
• Base-load current
I
H
A
2 × 2.6
2 × 4.3
2 × 7.7
2 × 15.3
•
I
max
-
C type
A
–
–
–
2 × 36
-
D type
A
2 × 9
2 × 15
2 × 27
2 × 54
Type rating
1)
• Based on
I
rated
kW
2 × 1.6
2 × 2.7
2 × 4.8
2 × 9.7
• Based on
I
H
kW
2 × 1.4
2 × 2.3
2 × 4.1
2 × 8.2
DC link current
I
d
2)
A
7.2
12
22
43
Current carrying capacity
• DC link busbars
A
100
100
100
100
• 24 V DC busbars
3)
A
20
20
20
20
DC link capacitance
μF
220
220
220
705
Power requirement at
24 V DC, maximum
A
0.9
0.9
0.9
1.1
Power loss
4)
typical/maximum
W
50/100
80/130
150/190
280/350
Cooling air requirement
m
3
/s
0.009
0.009
0.009
0.0155
Sound pressure level
L
pA
(1 m)
dB
<60
<60
<60
<60
Motor connection
U2, V2, W2
2 × plug connector
(X1, X2)
5)
,
2 × (1.5 ... 6 mm
2
)
2 × plug connector
(X1, X2)
5)
,
2 × (1.5 ... 6 mm
2
)
2 × plug connector
(X1, X2)
5)
,
2 × (1.5 ... 6 mm
2
)
2 × plug connector
(X1, X2)
5)
,
2 × (1.5 ... 6 mm
2
)
PE connection
M5 screw
M5 screw
M5 screw
M5 screw
Motor brake connection
Integrated into the plug-in motor connector (X1, X2), 24 V DC, 2 A
Motor cable length,
maximum
• Shielded
m
50
50
50
70
• Unshielded
m
75
75
75
100
Degree of protection
IP20
IP20
IP20
IP20
Width
mm
50
50
50
100
Height
mm
380
380
380
380
Depth
mm
270
270
270
270
Net weight
kg
4.7
4.7
4.7
7.7
1)
Rated power of a typical standard asynchronous motor at 600 V DC link voltage.
2)
Rated DC link current for dimensioning an external DC connection.
3)
If, due to a number of Line Modules and Motor Modules being mounted side-by-side, the current carrying capacity exceeds 20 A, an additional 24 V DC
connection using a 24 V terminal adapter is required (max. cross-section 6 mm
2
, max. fuse protection 20 A).
4)
Power loss of Motor Module at rated power including losses of 24 V DC electronics power supply.
5)
Connector not included in scope of supply
(see Accessories)
.
6)
At max. motor cable length 30 m, pulse frequency 4 kHz and DC link voltage 540 ... 600 V.
© Siemens AG 2016