Current derating for SINAMICS S150 drives as a function
of the pulse frequency
For control performance reasons or to increase output
frequency, the pulse frequency can be increased relative
to the factory setting. When the pulse frequency is
increased, the output current needs to be derated. This
derating factor must be applied to the currents specified
in the technical data.
An increased pulse frequency may also be used to reduce
motor noise. Note that SINAMICS S150 firmware also
includes functionality that allows an increased pulse
frequency without derating, when conditions permit (load,
ambient temperature, and input voltage). The pulse
frequency is
automatically reduced if the drive approaches
its thermal limits.
For additional information, please refer to the SINAMICS Low
Voltage Engineering Manual.
Rated
power at
460 (400) V
Rated
power at
460 V
Rated
output
current
I
N
Derating factor
at pulse frequency
Order No.
kW
HP
A
2.5 kHz
4 kHz
5 kHz
7.5 kHz
8 kHz
Line voltage 380 … 480 V 3ph. AC
6SL3710-7LE32-1AU3
125 (110)
150
210
95%
82%
74%
54%
50%
6SL3710-7LE32-6AU3
160 (132)
200
260
95%
83%
74%
54%
50%
6SL3710-7LE33-1AU3
200 (160)
250
310
97%
88%
78%
54%
50%
6SL3710-7LE33-8AU3
250 (200)
300
380
96%
87%
77%
54%
50%
6SL3710-7LE35-0AU3
300 (250)
400
490
94%
78%
71%
53%
50%
Derating factor of the output current as a function of the pulse frequency for units with a rated pulse frequency of 2 kHz
Rated
power at
460 (400) V or
575 (690) V
Rated
power at
460 V or
575V
Rated
output
current
I
N
Derating factor
at pulse frequency
Order No.
kW
HP
A
2 kHz
2.5 kHz
4 kHz
5 kHz
7.5 kHz
Line voltage 380 … 480 V 3ph. AC
6SL3710-7LE36-1AU3
355 (315)
500
605
83%
72%
64%
60%
40%
6SL3710-7LE37-5AU3
450 (400)
600
745
83%
72%
64%
60%
40%
6SL3710-7LE38-4AU3
500 (450)
700
840
87%
79%
64%
55%
40%
6SL3710-7LE41-0AU3
650 (560)
800
985
92%
87%
70%
60%
50%
6SL3710-7LE41-2AU3
800 (710)
1,000
1,260
92%
87%
70%
60%
50%
6SL3710-7LE41-4AU3
900 (800)
1,150
1,405
97%
95%
74%
60%
50%
Line voltage 500 … 600 V 3ph. AC
6SL3710-7LG28-5AU3
60 (75)
75
85
93%
89%
71%
60%
40%
6SL3710-7LG31-0AU3
75 (90)
100
100
92%
88%
71%
60%
40%
6SL3710-7LG31-2AU3
90 (110)
125
120
92%
88%
71%
60%
40%
6SL3710-7LG31-5AU3
110 (132)
150
150
90%
84%
66%
55%
35%
6SL3710-7LG31-8AU3
132 (160)
150
175
92%
87%
70%
60%
40%
6SL3710-7LG32-2AU3
160 (200)
200
215
92%
87%
70%
60%
40%
6SL3710-7LG32-6AU3
200 (250)
250
260
92%
88%
71%
60%
40%
6SL3710-7LG33-3AU3
250 (315)
300
330
89%
82%
65%
55%
40%
6SL3710-7LG34-1AU3
300 (400)
400
410
89%
82%
65%
55%
35%
6SL3710-7LG34-7AU3
350 (450)
450
465
92%
87%
67%
55%
35%
6SL3710-7LG35-8AU3
450 (560)
600
575
91%
85%
64%
50%
35%
6SL3710-7LG37-4AU3
560 (710)
700
735
87%
79%
64%
55%
25%
6SL3710-7LG38-1AU3
630 (800)
800
810
97%
95%
71%
55%
35%
6SL3710-7LG38-8AU3
750 (900)
900
910
92%
87%
67%
55%
33%
6SL3710-7LG41-0AU3
800 (1,000)
1,000
1,025
91%
86%
64%
50%
30%
6SL3710-7LG41-3AU3
1,000 (1,200)
1,250
1,270
87%
79%
55%
40%
25%
Derating factor of the output current as a function of the pulse frequency for units with a rated pulse frequency of 1.25 kHz
The following table lists the approx. maximum output frequency as a function of pulse frequency, at default 250
s current
controller clock cycle. Higher output frequencies are possible at higher pulse frequencies and current controller clock cycles as
low as 125
s:
Pulse frequency
Max. output frequency
1.25 kHz
100 Hz
2.00 kHz
160 Hz
2.50 kHz
200 Hz
≥ 4.00 kHz
300 Hz