Siemens D21.7
(Part 2) – 2015
3/2
Technical data
Electrical data
Supply voltages and output ranges
380 V to 480 V 3 ph AC, ±10% (-15% < 1 min) 150 to 1,150 HP
500 V to 600 V 3 ph AC, ±10% (-15% < 1 min) 75 to 1,250 HP
Supply systems
Grounded (TN/TT)
supplies or ungrounded (IT) supplies
Line frequency
47 Hz to 63 Hz
Output frequency
0 Hz to 550 Hz (higher output frequencies possible - consult factory)
Power factor fundamental / total
Preset to 1.0; adjustable
Converter efficiency
> 96%
Control method
Vector control (sensorless and closed loop) or V/Hz control
Fixed speeds
15 fixed speeds plus 1 minimum speed, programmable (in the default setting 3 fixed setpoints plus 1
minimum speed can be selected via digital inputs or bus communications)
Skipped frequency ranges
4, programmable
Setpoint resolution
0.001 rpm digital (14 bits + sign); 12 bit analog
Braking operation
Fully regenerative as standard; optional braking unit and resistor for braking if power fails
Mechanical data
Type of enclosure
NEMA1 (optionally NEMA 1 filtered or NEMA 12 ventilated)
Enclosure details
Rittal TS8, doors with double bit lock and 3-point latch, three section base plates for cable entry
Enclosure color
RAL 7035 light grey, indoor installation
Type of cooling
Forced air ventilation
Noise level LpA (1 m)
< 80 dB at 60 Hz line frequency
Environmental protection
Nickel plated busbars, varnish coated electronic boards
Compliance with standards
Standards
NEMA ICS 7, NEMA ICS 7.1, NEMA 250, NFPA79, UL508C for power module, ISO 13849-1, IEC 60146-1-1,
IEC 60204-1, IEC 60529, IEC 60508-1, IEC 61800-2, IEC 61800-3, IEC61800-5-1, IEC 61800-5-2
UL listing
Optional listing per UL508A
CE marking
In accordance with EMC directive No. 2004/108/EC and low-voltage directive No.2006/95/EC and Machinery
Directive No. 2006/42/EC for functional safety)
EMC conformance
EMC conformance is compliant with the EMC product standard for variable-speed drives IEC 61800-3 for the
“Second environment”, category C3 (industrial supply systems).
The equipment is not designed for connection to the “First environment” (public/ residential supply systems)
and may cause electromagnetic interference on a public system.
Ambient conditions
Operation
Storage
Transport
Ambient temperature
32°F to 104°F (0 °C to +40 °C)
-13°F (-25 °C) to 131°F
-13°F (-25 °C) to 158°F (+70 °C)
Up to +122°F (+50°C) with derating (+55 ºC)
Above -40°F (-40 °C) for 24 hours
Relative humidity (non-condensing)
5% to 95%
5% to 95%
5% to 95% at 40 ºC
Class 3K3 to IEC 60721-3-3
Class 1K4 to IEC 60721-3-1
Class 2K3 to IEC 60721-3-2
Environmental class/harmful
Class 3C2 to IEC 60721-3-3
Class 1C2 to IEC 60721-3-1
Class 2C2 to IEC 60721-3-2
chemical substances
Organic/biological influences
Class 3B1 to IEC 60721-3-3
Class 1B1 to IEC 60721-3-1
Class 2B1 to IEC 60721-3-2
Installation altitude
Up to 6,600 ft (2000 m) above sea level without reduction in performance, > 6,600 ft see derating data
Mechanical stability
Operation
Storage
Transport
Vibratory load
- Deflection
0.075 mm at 10 Hz to 58 Hz
1.5 mm at 5 Hz to 9 Hz
3.1 mm at 5 Hz to 9 Hz
- Acceleration
10 m/s
2
at > 58 Hz to 200 Hz
5 m/s
2
at > 9 Hz to 200 Hz
10 m/s
2
at > 9 Hz to 200 Hz
–
Class 1M2 to IEC 60721-3-1
Class 2M2 to IEC 60721-3-2
Shock load
- Acceleration
100 m/s
2
at 11 ms
40 m/s
2
at 22 ms
100 m/s
2
at 11 ms
Class 3M4 to IEC 60721-3-3
Class 1M2 to IEC 60721-3-1
Class 2M2 to IEC 60721-3-2
Deviations from the defined classes are identified by underlining.