SIEMENS
SINAMICS S150 NEMA
Enclosed drive
2
Siemens D21.7
(Part 2) – 2015
2/12
2/13
Description of options
It is delivered already mounted to
the enclosure. The height of the
operator panel changes accordingly.
The base is always colored RAL 7022
(umbra grey). A special color is
not possible.
M07
Base (plinth) 8” (200mm) high
The 8” enclosure base provides more space for bending
and routing cables. The base is delivered already mounted
to the enclosure. The height of the operator panel
changes accordingly.
The base color is the same as the enclosure, RAL 7035 (light
grey). If the enclosure is ordered in a special color (option
Y09), the 8” base is also painted the same color.
M13
Line side top cable entry
This option provides copper stabs and a ground connection
in the tophat (only for drives with input current rating >800
A @ 460 V, >600 A @ 575 V. For smaller ratings cables can
enter from top or bottom).
M23
Enclosure NEMA 1 filtered
Louvers and foam air filters are added to air inlet and outlet
openings (IP23). A NEMA 1 filtered enclosure is required to
meet the requirements for listing the enclosed drive
per UL508A.
M43
Enclosure IP43
Similar to NEMA 1 filtered (M23), but additionally a 1 mm
wire mesh is provided behind the air filters.
M54
Enclosure NEMA 12 (ventilated)
Louvers and fine paper air filters are added to air inlet and
outlet openings (IP54), to prevent even fine dust particles
from entering the enclosure in very dusty environments.
These fine dust filters are a patented design for high volume
airflow with small derating. The drive current must be
derated with a NEMA 12 filtered enclosure – refer to derating
values on page 3/3.
M78
Motor side top cable exit
This option provides copper stabs and a ground connection
in the tophat above the power module, for connecting motor
cables entering the enclosure from above.
If option L61 or L62 is selected together with option M78,
the braking resistor should also be connected from above.
Note that the combination of standard options M78 with L08
(motor reactor) or L10 (dV/dt filter) is not possible. Please
consult factory if this combination is required.
M90
Lifting beams
Note: Option M90 is strongly
recommended, to enable lifting
the drives off their pallet safely.
Once the drives are in position, the
lifting hardware needs to be removed to
mount the tophats. For multiple drives
with identical enclosure sizes, option
M90 can be ordered once and the
hardware re-used for other units.
N55
ALL STOP, coast to stop
A mushroom style, latching, twist-to-release, padlockable
push button is mounted on the door wired to OFF2. The
motor coasts to stop.
This function is a basic single channel stop circuit. With an
input contactor (options L13, L29 or L30), the drive can also
be isolated from the supply.
N57
EMERGENCY OFF category 0, coast to stop, 120 V AC
or 24 V DC
EMERGENCY OFF Category 0 for uncontrolled stop in
accordance with IEC 60204-1
The function bypasses the microprocessor controller by
means of a safety relay combination in accordance with
IEC 60204-1, and disconnects the drive from the line by
opening the input contactor. The motor coasts to stop.
A mushroom style, latching, twist-to-release, padlockable
push button is mounted on the door. When delivered, the
button circuit is preset to 120 V AC. Jumpers must be set
when using 24 V DC.
N59
EMERGENCY STOP category 1, controlled ramp down,
120 V AC
EMERGENCY STOP Category 1 for controlled stop in
accordance with IEC 60204-1, 120 V AC circuit.
The function includes a fast ramp down of the drive (to be
parameterized by the user). This is followed by disconnecting
the drive from the supply as described for the EMERGENCY
OFF category 0.
A mushroom style, latching, twist-to-release, padlockable
push button is mounted on the door.
A braking unit may be necessary to achieve the required
shutdown times also in the event of a power failure.
Enclosure with option M06
SINAMICS drive on pallet
with transportation beams