SIEMENS
13/44
Siemens D 21.4 · 2017
Tools and configuration
Configuration notes
Mechanical configuration of the drive system
13
■
Configuration
(continued)
Motor Module
booksize format
I
rated
Recommended cable
cross-section
for Cu conductors and
PVC insulation with a
permissible operating
temperature of 70 °C
(158°F) on the conductor
DC link rectifier adapter
LV HRC fuse
with knife contacts
with screw contacts
A
mm
2
Article No.
A
Article No.
Article No.
3
2.5
6SL3162-2BD00-0AA0
16
3NE8015-1
3NE8715-1
5
2.5
16
3NE8015-1
3NE8715-1
9
4
35
3NE8017-1
3NE8717-1
18
10
63
3NE8018-1
3NE8718-1
30
10
80
3NE8020-1
3NE8720-1
45
35
6SL3162-2BM00-0AA0
125
3NE8022-1
3NE8722-1
60
70
160
3NE8024-1
3NE8724-1
85
95
200
3NE3227
3NE8727-1
132
95
315
3NE3230-0B
3NE8731-1
200
95
400
3NE3230-0B
3NE8731-1
2 × 3
2.5
6SL3162-2BD00-0AA0
20
3NE8015-1
3NE8715-1
2 × 5
4
35
3NE8017-1
3NE8717-1
2 × 9
10
63
3NE8018-1
3NE8718-1
2 × 18
10
125
3NE8022-1
3NE8722-1
© Siemens AG 2017