SIEMENS
13/16
Siemens D 21.4 · 2017
Tools and configuration
Configuration notes
EMC notes for the application of the product standard EN 61800-3
13
■
Configuration
(continued)
Maximum permissible cable lengths from the motor to the converter when using output reactors or filters
depending on the voltage range and the Power Module being used
The following load-side power components in the appropriate
frame sizes are optionally available for the Power Modules and
result in the following maximum cable lengths:
■
More information
Converters are equipment used on a professional basis, de-
ployed in certain areas of business and industry – and are not
operated in the general public domain.
For EMC-compliant installation, observe the information in the
Configuration Manual EMC installation guideline:
Maximum permissible motor cable lengths (shielded/unshielded) in m (ft)
Frame size
FSA
FSB
FSC
FSD
FSE
FSF
PM240-2 Power Module with integrated braking chopper
Available frame sizes
• 200 V versions
• 400 V versions
• 690 V versions
–
–
–
With optional output reactor
• At 200 ... 240 V 1 AC/3 AC
150/225
(492/738)
150/225
(492/738)
150/225
(492/738)
–
–
–
• At 380 ... 415 V 3 AC
150/225
(492/738)
150/225
(492/738)
150/225
(492/738)
200/300
(656/984)
3)
200/300
(656/984)
3)
300/450
(984/1476)
3)
• At 440 ... 480 V 3 AC
100/150
(328/492)
100/150
(328/492)
100/150
(328/492)
200/300
(656/984)
3)
200/300
(656/984)
3)
300/450
(984/1476)
3)
• At 500 ... 690 V 3 AC
–
–
–
200/300
(656/984)
3)
200/300
(656/984)
3)
300/450
(984/1476)
3)
With integrated line filter class A
• At 200 ... 240 V 1 AC/3 AC
50/- (164/-)
50/- (164/-)
50/- (164/-)
–
–
–
• At 380 ... 480 V 3 AC
50/- (164/-)
100/- (328/-)
2)
150/- (492/-)
2)
150/- (492/-)
150/- (492/-)
150/- (492/-)
• At 500 ... 690 V 3 AC
–
–
–
100/- (328/-)
100/- (328/-)
150/- (492/-)
(category C3)
With optional, external line filter
class B according to EN 55011 to
comply with cable-conducted radio
interference emissions according
to EN 61800-3 EMC Category C1
1)
,
together with unfiltered
Power Modules
• At 380 ... 480 V 3 AC
50/- (164/-)
50/- (164/-)
50/- (164/-)
–
–
–
With optional, external line filter
class B according to EN 55011 and
output reactor to comply with radio
interference emissions according
to EN 61800-3 EMC Category C2
1)
,
together with unfiltered
Power Modules
• At 380 ... 415 V 3 AC
150/- (492/-)
150/- (492/-)
150/- (492/-)
–
–
–
• At 440 ... 480 V 3 AC
100/- (328/-)
100/- (328/-)
100/- (328/-)
–
–
–
1)
Further information is available on the Internet at
/sinamics-g120/documentation
2)
The values apply for cables with low capacitance, e.g. MOTION-CONNECT.
When using standard CY cables, the maximum motor cable length is 50 m
(164 ft) (shielded).
3)
The maximal cable lengths for frame sizes FSD to FSF will not be increased
with a motor reactor. The motor reactor reduces the load on the motor
windings by reducing the voltage gradients (du/dt).
© Siemens AG 2017