SIEMENS
13/14
Siemens D 21.4 · 2017
Tools and configuration
Configuration notes
EMC notes for the application of the product standard EN 61800-3
13
■
Configuration
SINAMICS S120 Power Drive Systems (PDS) can be operated in the first and second environments. The measures necessary for
operation in the respective environment are subsequently listed.
Measures for complying with product standard EN 61800-3 second environment
Interference immunity
The SINAMICS S120 drive system is suitable for operation in the
second environment.
Regarding interference immunity, SINAMICS S120 can be used
in the
first and second environments
.
Interference emission – complying with Category C2
second environment
Regarding interference emission, to comply with the limit values
according to EN
61800-3 second environment, Category C2, the
following measures must be applied:
•
The drive system must be installed in compliance with EMC
regulations by appropriately trained professionals.
•
The SINAMICS S120 drive system requires a radio inter-
ference suppression filter, Category C2 (integrated as line
filter, or as optional external line filter with/without line reactor)
•
The pulse frequency is less than or equal to the rated pulse
frequency
•
The maximum motor cable length is complied with (shielded)
•
Line supply with grounded neutral point (TN/TT supply
system)
Device-specific assignment of the measures to comply with product standard EN 61800-3 second environment, Category C2
Interference emission – complying with Category C3
second environment
All Active Line Modules in booksize format, Basic Line Modules
in booksize format 100 kW as well as Line Modules in chassis
format in the standard version are compliant.
A line reactor is required for Power Modules in chassis format.
The maximum cable lengths and pulse frequencies (see the
previous table) must be taken into account.
For Active Line Modules in booksize format, when using an
external line filter, the maximum cable length can be increased
to 1000 m (3281 ft).
Interference emission – complying with Category C4
second environment
When connected to IT line supplies, only devices without inte-
grated filter, Basic Line Modules in booksize format up to 40 kW,
and all Smart Line Modules in booksize format are permissible.
To limit symmetrical interference emission, suitable external
filters without capacitors connected to ground must be used.
Further selected accessories are available from "Siemens
Product Partner for Drives Options":
/drives-options-partner
SINAMICS S120 drive system
Measures for
Radio interference suppression filter,
Category C2
Maximum pulse
frequency
f
p
Maximum motor cable
length (shielded)
Device format
Supply voltage
Frame size
kHz
m (ft)
Booksize
Line Modules
380 ... 480 V 3 AC
–
External line filter required
1)
4
2)
350 (1148)
Chassis
Active Line Modules
Smart Line Modules
380 ... 480 V 3 AC
FX ... JX
External line filter required
4
2)
300 (984)
500 ... 690 V 3 AC
FX ... JX
External line filter required
4
2)
300 (984)
Chassis
Basic Line Modules
380 ... 480 V 3 AC
FB ... GD
External line filter plus line reactor required
1)
4
2)
100 (328)
500 ... 690 V 3 AC
FB ... GD
External line filter plus line reactor required
1)
4
2)
100 (328)
Chassis
Power Modules
380 ... 480 V 3 AC
FX and GX
External line filter
plus line reactor required
1)
2
100 (328)
Blocksize
Power Modules with
integrated line filter
200 ... 240 V 1/3 AC
FSA ... FSC
No measure required,
as a line filter is integrated
4
50 (164)
380 ... 480 V 3 AC
FSA ... FSC
No measure required,
as a line filter is integrated
4
50 (164)
FSD ... FSE
No measure required,
as a line filter is integrated
4
150 (492)
FSF
No measure required,
as a line filter is integrated
2
150 (492)
500 ... 690 V 3 AC
FSD and FSE
No measure required,
as a line filter is integrated
2
100 (328)
FSF
No measure required
as a line filter is integrated
(Category C3)
2
150 (492)
Blocksize
Power Modules
without integrated
line filter
200 ... 240 V 3 AC
FSD ... FSF
External line filter required
4
150 (492)
380 ... 480 V 3 AC
FSA ... FSC
External line filter required
1)
4
50 (164)
FSD ... FSE
External line filter required
1)
4
150 (492)
FSF
External line filter required
1)
2
150 (492)
500 ... 690 V 3 AC
FSD ... FSF
External line filter required
1)
2
100 (328)
1)
Selection and ordering data for line filters and line reactors
see sections Line-side power components
.
2)
Refers to the pulse frequency of the Motor Modules.
© Siemens AG 2017