SIEMENS
12/25
Siemens D 21.4 · 2017
MOTION-CONNECT connection systems
Signal cables for SINAMICS S120
12
■
Technical specifications
(continued)
Degree of protection of the pre-assembled signal cables and their extensions when closed and inserted: IP67.
Signal cables
MOTION-CONNECT 500
MOTION-CONNECT 800PLUS
6FX50..-
.....
-
....
6FX80..-
.....
-
....
Certificate of suitability
• cURus or UR/CSA
UL758-CSA-C22.2-N.210.2-M90
UL758-CSA-C22.2-N.210.2-M90
• UR-CSA File No.
1)
Yes
Yes
• RoHS conformity
Yes
Yes
Rated voltage
according to EN 50395
30 V
30 V
Test voltage, rms
500 V
500 V
Operating temperature on the surface
• Fixed installation
-20 … +80 °C (-4 ... +176 °F)
-50 … +80 °C (-58 ... +176 °F)
• Flexible installation
0 … 60 °C (32 ... 140 °F)
-20 … +60 °C (-4 ... +140 °F)
Tensile stress, max.
• Fixed installation
50 N/mm
2
(7252 lb/in
2
)
50 N/mm
2
(7252 lb/in
2
)
• Flexible installation
20 N/mm
2
(2901 lb/in
2
)
20 N/mm
2
(2901 lb/in
2
)
Smallest bending radius
• Fixed installation
60 mm (2.36 in)
4
×
D
max
• Flexible installation
100 mm (3.94 in)
70 mm
2)
(2.75 in)
Torsional stress
Absolute 30°/m
Absolute 30°/m
Bending
2 million
10 million
Traversing velocity
180 m/min (591 ft/min)
Up to 300 m/min (984 ft/min)
Acceleration
5 m/s
2
(16.41 ft/s
2
)
Up to 50 m/s
2
(164 ft/s
2
),
see characteristics on page 12/5
Insulation material, incl. jacket
CFC/silicone-free
CFC/halogen-free/silicon-free
IEC 60754-1/DIN VDE 0472-815
Oil resistance
EN 60811-2-1 (mineral oil only)
EN 60811-2-1
Outer jacket
PVC
PUR, HD22.10 S2 (VDE 0282, Part 10)
DESINA color green RAL 6018
DESINA color green RAL 6018
Flame-retardant
EN 60332-1-1 to 1-3
EN 60332-1-1 to 1-3
1)
The File No. is printed on the cable jacket.
2)
Exception: 6FX8002-2SL..-
....
; smallest bending radius (flexible): 85 mm (3.35 in).
© Siemens AG 2017