SIEMENS
7/33
Siemens D 21.4 · 2017
SINAMICS S120 drive system
Booksize format
Active Line Modules in booksize format
7
■
Technical specifications
(continued)
Line voltage 380 ... 480 V 3 AC
Active Line Module in booksize format
Internal air cooling
6SL3130-
7TE21-6AA4
6SL3130-
7TE23-6AA3
6SL3130-
7TE25-5AA3
6SL3130-
7TE28-0AA3
6SL3130-
7TE31-2AA3
Infeed/regenerative feedback power
• Rated power
P
rated
-
At 380 V 3 AC
kW
16
36
55
80
120
-
At 460 V 3 AC
5)
(hp)
(18)
(40)
(60)
(100)
(150)
• For S6 duty
P
S6
(40 %)
kW
21
47
71
106
145
•
P
max
kW
35
70
91 (122)
1)
)
131
175
DC link current
• At 600 V DC
A
27
60
92
134
200
• For S6 duty (40 %)
A
35
79
121
176
244
• Maximum
A
59
117
152 (176
1)
)
218
292
Input current
• Rated current
at 380/400/480 V 3 AC
A
26/25/21
58/55/46
88/84/70
128/122/102
192/182/152
• For S6 duty (40 %) at 400 V
A
32
71
108
161
220
• At 400 V max.
A
54
107
139 (168
1)
)
200
267
Current requirement
24 V DC electronics power supply, max.
A
1.1
1.5
1.9
2
2.5
Current carrying capacity
• 24 V DC busbars
A
20
20
20
20
20
• DC link busbars
A
100
200
200
200
200
DC link capacitance
• Active Line Module
μ
F
710
1410
1880
2820
3995
• Drive line-up, max.
μ
F
20000
20000
20000
20000
20000
Power loss
2)
kW
0.28
0.67
0.95
1.38
2.24
Cooling air requirement
m
3
/s
(ft
3
/s)
0.016 (0.57)
0.031 (1.09)
0.044 (0.155)
0.144 (4.1)
0.144 (4.1)
Sound pressure level
L
pA
(1 m)
dB
<60
<65
<60
<73
<73
Line connection
U1, V1, W1
Screw-type
terminals (X1)
M6 screw studs
(X1)
M8 screw studs
(X1)
M8 screw studs
(X1)
M8 screw studs
(X1)
• Conductor cross-section, max.
mm
2
2.5 ... 10
2.5 ... 50
2.5 ... 95, 2 × 35
2.5 ... 120, 2 × 50
2.5 ... 120, 2 × 50
Shield connection
Integrated in the
connector
See Accessories
See Accessories
See Accessories
See Accessories
PE connection
M5 screw
M6 screw
M6 screw
M8 screw
M8 screw
Cable length, max.
Total of all motor cables and DC link
• Shielded
m (ft)
630 (2067)
3)
630 (2067)
3)
1000 (3281)
1000 (3281)
1000 (3281)
• Unshielded
m (ft)
850 (2789)
850 (2789)
1500 (4922)
1500 (4922)
1500 (4922)
Degree of protection
IP20
IP20
IP20
IP20
IP20
Dimensions
• Width
mm (in)
100 (3.94)
150 (5.91)
200 (7.87)
300 (11.81)
300 (11.81)
• Height
mm (in)
380 (14.96)
380 (14.96)
380 (14.96)
380 (14.96)
380 (14.96)
-
With fan
4)
mm (in)
–
–
–
629 (24.76)
629 (24.76)
• Depth
mm (in)
270 (10.63)
270 (10.63)
270 (10.63)
270 (10.63)
270 (10.63)
Weight, approx.
kg (lb)
7 (15.4)
10 (22.0)
17 (37.5)
23 (50.7)
23 (50.7)
1)
Higher peak output is possible in combination with the Active Interface
Module 6SL3100-0BE25-5AB0
(for operating cycle constraints, see
SINAMICS S120 Manual)
.
2)
Power loss of Active Line Module at rated output including losses of 24 V
DC electronics power supply.
3)
Max. cable lengths in combination with Active Interface Module and Basic
Line Filter (Category C3 according to EN 61800-3).
4)
The fan is supplied together with the Active Line Module and must be
installed before the Active Line Module is commissioned.
5)
Nominal hp ratings are provided for ease of assigning components only.
The Line Module outputs are dependent on the Motor Module loading and
are to be dimensioned accordingly.
© Siemens AG 2017