SIEMENS
7/265
Siemens D 21.4 · 2017
SINAMICS S120 drive system
Blocksize format
Recommended line-side power components for blocksize format
7
■
Selection and ordering data
The following tables list recommendations for additional line-
side components, such as fuses and circuit breakers. The
values in the table take into account the overload capability of
the inverter.
Notes
for use in compliance with IEC standards:
3NA3 or 3NE1 fuses and 3RV motor starter protectors or 3VL
circuit breakers are recommended for European countries.
Notes
for use in compliance with UL regulations:
UL-listed fuses Class J, T, CC, G or CF (with rated voltage
250 V AC or 600 V AC) or 3NE1 (UL-compliant – corresponds to
RU) are required for North America.
Short Circuit Current Rating (SCCR)
according to UL
Applies to industrial control panel installations to
NEC Article 409 or UL 508A/508C
•
PM240-2: 100 kA (200 V versions), 100 kA (400 V versions),
65 kA (690 V versions)
(the value depends on the fuses and circuit breakers used)
Notes
regarding installations in Canada:
Overvoltage protection devices in accordance with overvoltage
category III and with the following ratings must be connected on
the line side of the inverter:
•
Rated voltage 480 V (phase-phase) and 480 V
(phase-ground)
•
Voltage limit 4 kV (phase-phase) and 6 kV (phase-ground)
All overvoltage protection devices used must comply with
Canadian standards for industrial installations.
Further information, particularly regarding use in accordance
with UL guidelines, is available at
Additional information about the line-side power components
can be found in Catalogs LV 10, IC 10 and IC 10 AO as well as
the Industry Mall.
1)
Type rating based on the rated output current
I
rated
. The rated output
current
I
rated
is based on the duty cycle for low overload (LO).
*)
See Catalog LV 10 for Article No. supplements.
Type rating
1)
PM240-2
Power Module
standard variant
IEC-compliant
UL/cUL-compliant
Fuse
Circuit breaker
Fuse type
Rated voltage
250 V AC or 600 V AC
Type
Current
Current
kW
hp
6SL3210-...
Frame size
A
Article No.
Article No.
Class
A
200 ... 240 V 1 AC/3 AC
0.55
0.75
1PB13-0 . L0
FSA
16
3NA3805
3RV2011-4AA10
J, T, CC, G, CF
15
0.75
1
1PB13-8 . L0
FSA
16
3NA3805
3RV2011-4AA10
J, T, CC, G, CF
15
1.1
1.5
1PB15-5 . L0
FSB
32
3NA3812
3RV2021-4EA10
J, T, CC, G, CF
35
1.5
2
1PB17-4 . L0
FSB
32
3NA3812
3RV2021-4EA10
J, T, CC, G, CF
35
2.2
3
1PB21-0 . L0
FSB
32
3NA3812
3RV2021-4EA10
J, T, CC, G, CF
35
3
4
1PB21-4 . L0
FSC
50
3NA3820
3RV1031-4HA10
J, T, CC, G, CF
50
4
5
1PB21-8 . L0
FSC
50
3NA3820
3RV1031-4HA10
J, T, CC, G, CF
50
200 ... 240 V 3 AC
5.5
7.5
1PC22-2 . L0
FSC
50
3NA3820
3RV1031-4HA10
J, T, CC, G, CF
50
7.5
10
1PC22-8 . L0
FSC
50
3NA3820
3RV1031-4HA10
J, T, CC, G, CF
50
11
15
1PC24-2UL0
FSD
63
3NE1818-0
3RV1041-4JA10
J
60
15
20
1PC25-4UL0
FSD
80
3NE1820-0
3RV1041-4KA10
J
70
18.5
25
1PC26-8UL0
FSD
100
3NE1021-0
3RV1041-4LA10
J
90
22
30
1PC28-0UL0
FSE
100
3NE1021-0
3VL1712-2DD33-
....
*)
J
100
30
40
1PC31-1UL0
FSE
160
3NE1224-0
3VL1716-2DD33-
....
*)
J
150
37
50
1PC31-3UL0
FSF
200
3NE1225-0
3VL3720-3DC33-
....
*)
J
175
45
60
1PC31-6UL0
FSF
200
3NE1225-0
3VL3720-3DC33-
....
*)
J
200
55
75
1PC31-8UL0
FSF
250
3NE1227-0
3VL3725-3DC33-
....
*)
J
225
380 ... 480 V 3 AC
0.55
0.75
1PE11-8 . L1
FSA
16
3NA3805
3RV2011-4AA10
J, T, CC, G, CF
10
0.75
1
1PE12-3 . L1
FSA
16
3NA3805
3RV2011-4AA10
J, T, CC, G, CF
10
1.1
1.5
1PE13-2 . L1
FSA
16
3NA3805
3RV2011-4AA10
J, T, CC, G, CF
15
1.5
2
1PE14-3 . L1
FSA
16
3NA3805
3RV2011-4AA10
J, T, CC, G, CF
20
2.2
3
1PE16-1 . L1
FSA
16
3NA3805
3RV2011-4AA10
J, T, CC, G, CF
30
3
4
1PE18-0 . L1
FSA
16
3NA3805
3RV2011-4AA10
J, T, CC, G, CF
30
4
5
1PE21-1 . L0
FSB
32
3NA3812
3RV2021-4EA10
J, T, CC, G, CF
35
5.5
7.5
1PE21-4 . L0
FSB
32
3NA3812
3RV2021-4EA10
J, T, CC, G, CF
35
7.5
10
1PE21-8 . L0
FSB
32
3NA3812
3RV2021-4EA10
J, T, CC, G, CF
35
11
15
1PE22-7 . L0
FSC
50
3NA3820
3RV1031-4HA10
J, T, CC, G, CF
50
© Siemens AG 2017