SIEMENS
7/251
Siemens D 21.4 · 2017
SINAMICS S120 drive system
Blocksize format
Air-cooled Power Modules in blocksize format
7
■
Technical specifications
(continued)
Line voltage 380 ... 480 V 3 AC
PM240-2 Power Modules standard variant
Without integrated line filter
6SL3210-1PE31-5UL0
6SL3210-1PE31-8UL0
6SL3210-1PE32-1UL0
6SL3210-1PE32-5UL0
With integrated line filter class A
6SL3210-1PE31-5AL0
6SL3210-1PE31-8AL0
6SL3210-1PE32-1AL0
6SL3210-1PE32-5AL0
Output current
at 50 Hz 400 V 3 AC
• Rated current
I
rated
1)
A
145
178
205
250
• For S6 duty (40 %)
I
S6
A
174
213
246
300
• Base-load current
I
H
2)
A
110
145
178
205
• Maximum current
I
max
A
220
290
356
410
Type rating
• Based on
I
rated
kW (hp)
75 (100)
90 (125)
110 (150)
132 (200)
• Based on
I
H
kW (hp)
55 (75)
75 (100)
90 (125)
110 (150)
Rated pulse frequency
kHz
4
4
2
2
Efficiency
η
%
>97
>97
>97
>97
Power loss
3)
at rated current
kW
1.79
2.33
2.17
2.84
Cooling air requirement
m
3
/s (ft
3
/s)
0.2 (7.1)
0.2 (7.1)
0.2 (7.1)
0.2 (7.1)
Sound pressure level
L
pA
(1 m)
dB
56 ... 68
4)
56 ... 68
4)
56 ... 68
4)
56 ... 68
4)
24 V DC power supply
for Control Unit
A
1
1
1
1
Input current
5)
• Rated current
A
149
183
211
257
• Based on
I
H
A
117
154
189
218
Line supply connection
U1/L1, V1/L2, W1/L3
M10 screw stud
M10 screw stud
M10 screw stud
M10 screw stud
• Conductor cross-section
mm
2
35 ... 2 × 120
35 ... 2 × 120
35 ... 2 × 120
35 ... 2 × 120
Motor connection
U2, V2, W2
M10 screw stud
M10 screw stud
M10 screw stud
M10 screw stud
• Conductor cross-section
mm
2
35 ... 2 × 120
35 ... 2 × 120
35 ... 2 × 120
35 ... 2 × 120
PE connection
M10 screw stud
M10 screw stud
M10 screw stud
M10 screw stud
Motor cable length, max.
• Shielded
m (ft)
300 (984)
300 (984)
300 (984)
300 (984)
• Unshielded
m (ft)
450 (1476)
450 (1476)
450 (1476)
450 (1476)
Degree of protection
IP20
IP20
IP20
IP20
Dimensions
• Width
mm (in)
305 (12.01)
305 (12.01)
305 (12.01)
305 (12.01)
• Height
mm (in)
708 (27.87)
708 (27.87)
708 (27.87)
708 (27.87)
• Depth without operator panel
mm (in)
357 (14.06)
357 (14.06)
357 (14.06)
357 (14.06)
Frame size
FSF
FSF
FSF
FSF
Weight, approx.
• Without integrated line filter
kg (lb)
57 (126)
57 (126)
61 (135)
61 (135)
• With integrated line filter
kg (lb)
63 (139)
63 (139)
65 (143)
65 (143)
1)
The rated output current
I
rated
is based on the duty cycle for low overload
(LO).
2)
The base-load current
I
H
is based on the duty cycle for high overload
(HO).
3)
Typical values. You can find additional information on the Internet at
4)
Values dependent on ambient temperature and utilization.
5)
The input current depends on the motor load and line impedance. The
input currents apply for a load with the type rating (based on
I
rated
) for a
line impedance corresponding to
u
k
= 1 %. The current values are
specified on the rating plate of the Power Module.
© Siemens AG 2017