SIEMENS
7/242
Siemens D 21.4 · 2017
SINAMICS S120 drive system
Blocksize format
Air-cooled Power Modules in blocksize format
7
■
Technical specifications
General technical specifications
Unless explicitly specified otherwise, the following technical
specifications are valid for all PM240-2 Power Modules in the
blocksize format, FSA to FSF.
Note:
When engineering the complete SINAMICS S120 drive, the
system data of the associated Control Units, supplementary
system components, DC link components and Sensor Modules
must be taken into consideration.
Footnotes see next page.
Electrical specifications
Line voltage
• Blocksize format FSA ... FSC
200 to 240 V 1 AC ±10 %
200 to 240 V 3 AC ±10 %
380 to 480 V 3 AC ±10 %
• Blocksize format FSD to FSF
200 … 240 V 3 AC ±10 % (in operation -20 % <1 min)
380 ... 480 V 3 AC ±10 % (in operation -20 % <1 min)
500 … 690 V 3 AC ±10 % (in operation -20 % <1 min)
Line system configurations
Grounded TN/TT systems and non-grounded IT systems
Line frequency
47 ... 63 Hz
Line power factor
for a 3 AC line supply voltage and output power
• Blocksize format FSA ... FSC
-
Fundamental power factor (cos
ϕ
1
)
>0.96
-
Total (
λ
)
> 0.7 – 0.85
• Blocksize format FSD to FSF
-
Fundamental power factor (cos
ϕ
1
)
> 0.98 – 0.99
-
Total (
λ
)
> 0.9 – 0.92
Electromagnetic compatibility
1)
• Interference immunity
All PM240-2 Power Modules are suitable for use in both the first and second environments.
• Interference emission acc. to EN 61800-3
Second environment
-
For devices with integrated radio suppression
interference filter
Category C2
-
For devices with integrated radio suppression
interference filter, format FSF with a line
supply voltage of 690 V
Category C3
-
For devices without integrated radio
interference suppression filter with optional
external radio interference filter for grounded
line supplies
Category C2
(recommended for operation in conjunction with a residual current protective device RCD)
-
For devices without integrated radio
interference suppression filter for operation
on IT line supplies
Category C4
• Interference emission acc. to EN 61800-3
First environment
Can be used in the first environment when taking into consideration the additional secondary conditions
listed in Section, EMC notes
Overvoltage category
acc. to IEC/EN 61800-5-1
III
Electronics power supply
implemented as PELV circuit according to
IEC/EN 61800-5-1
24 V DC, -15 % +20 %
Ground = negative pole grounded via the electronics
Short-circuit current rating (SCCR)
(S
hort C
ircuit C
urrent R
ating)
Applies to industrial control cabinet installations
according to NEC Article 409 or UL 508A
100 kA
See the recommended line-side components
–
the value depends on the fuses and circuit breakers used
Rated pulse frequency
• For devices with a rated voltage of
200 V 1/3 AC, 400 V 3 AC and a type rating
≤
90 kW based on
I
rated
4 kHz
• For devices with a rated voltage of 690 V 3 AC
and a type rating
≥
110 kW based on
I
rated
2 kHz
Output voltage, max.
Approximately 0.95 × line voltage
(at 200 V 1 AC, approximately 0.74 × line voltage)
Output frequency
0 ... 550 Hz
(dependencies on the control mode and pulse frequency must be taken into account)
© Siemens AG 2017