SIEMENS
7/223
Siemens D 21.4 · 2017
SINAMICS S120 drive system
Chassis format
Motor-side power components for chassis format
> Motor reactors
7
■
Technical specifications
(continued)
Line voltage 500 ... 690 V 3 AC
Motor reactor (for pulse frequencies of 1.25 kHz to 2.5 kHz)
6SL3000-2AH38-1AA0
6SL3000-2AH41-0AA0
6SL3000-2AH41-1AA0
6SL3000-2AH41-3AA0
Rated current
A
810
910
1025
1270
Power loss, max.
1)
kW
1.0
0.97
1.05
0.95
Load connection
Flat connector for
M12 screw
Flat connector for
M12 screw
Flat connector for
M12 screw
Flat connector for
M12 screw
PE connection
M8 screw
M8 screw
M8 screw
M8 screw
Cable length, max.
between the motor reactor and motor
(number of reactors in series)
(1)
(2)
(1)
(2)
(1)
(2)
(1)
(2)
• Shielded
m (ft)
300 (984)
525 (1723)
300 (984)
525 (1723)
300 (984)
525 (1723)
300 (984)
525 (1723)
• Unshielded
m (ft)
450 (1476)
787 (2582)
450 (1476)
787 (2582)
450 (1476)
787 (2582)
450 (1476)
787 (2582)
Degree of protection
IP00
IP00
IP00
IP00
Dimensions
• Width
mm (in)
410 (16.1)
410 (16.1)
410 (16.1)
460 (18.1)
• Height
mm (in)
392 (15.4)
392 (15.4)
392 (15.4)
392 (15.4)
• Depth
mm (in)
279 (11.0)
279 (11.0)
317 (12.5)
296 (11.6)
Weight, approx.
kg (lb)
146 (322)
150 (331)
163 (359)
153 (337)
Suitable for Motor Module
6SL3320-1TG38-1AA3
6SL3325-1TG38-0AA3
6SL3325-1TG38-1AA3
6SL3320-1TG38-8AA3
6SL3320-1TG41-0AA3
6SL3325-1TG41-0AA3
6SL3320-1TG41-3AA3
6SL3325-1TG41-3AA3
• Rated current of the Motor Module
A
810
910
1025
1270
• Type rating of the Motor Module
kW
800
900
1000
1200
1)
The specified power loss represents the maximum value at 100 % utilization.
The value is lower under normal operating conditions.
© Siemens AG 2017