Chassis format
Line-side power components for chassis format
> Recommended line-side system components
7
■
Selection and ordering data
(continued)
Assignment of line-side power components to air-cooled and liquid-cooled Active Line Modules or
Active Interface Modules in chassis format
Rated output
at 400 V, 50 Hz (460 V, 60 Hz) or
690 V, 50 Hz (575 V, 60 Hz)
Rated input current
Suitable for
Active Interface Module
Suitable for
Active Line Module
Bypass contactor
kW (hp)
A
Article No.
Line voltage 380 ... 480 V 3 AC
132 (200)
210
6SL3300-7TE32-6AA0
6SL3330-7TE32-1AA3
Included in
Active Interface Module
160 (250)
260
6SL3300-7TE32-6AA0
6SL3330-7TE32-6AA3
Included in
Active Interface Module
235 (400)
380
6SL3300-7TE33-8AA0
6SL3330-7TE33-8AA3
Included in
Active Interface Module
300 (500)
490
6SL3300-7TE35-0AA0
6SL3330-7TE35-0AA3
6SL3335-7TE35-0AA3
Included in
Active Interface Module
380 (600)
605
6SL3300-7TE38-4AA0
6SL3330-7TE36-1AA3
6SL3335-7TE36-1AA3
3RT1476-6AP36
500 (700)
840
6SL3300-7TE38-4AA0
6SL3330-7TE38-4AA3
6SL3335-7TE38-4AA3
3WL1110-2BB34-4AN2-Z
C22
1)
630 (900)
985
6SL3300-7TE41-4AA0
6SL3330-7TE41-0AA3
6SL3335-7TE41-0AA3
3WL1112-2BB34-4AN2-Z
C22
1)
800 (1000)
1260
6SL3300-7TE41-4AA0
6SL3330-7TG37-4AA3
3WL1116-2BB34-4AN2-Z
C22
1)
900 (1250)
1405
6SL3300-7TE41-4AA0
6SL3305-7TE41-4AA3
6SL3330-7TE41-4AA3
6SL3335-7TE41-4AA3
3WL1116-2BB34-4AN2-Z
C22
1)
Line voltage 500 ... 690 V 3 AC
630 (675)
575
6SL3300-7TG35-8AA0
6SL3330-7TG35-8AA3
6SL3335-7TG35-8AA3
3RT1476-6AP36
800 (900)
735
6SL3300-7TG37-4AA0
6SL3305-7TG37-4AA3
6SL3330-7TG37-4AA3
6SL3335-7TG37-4AA3
3RT1476-6AP36
(3 units)
900 (975)
810
6SL3300-7TG41-3AA0
6SL3335-7TG38-1AA3
3WL1110-2BB34-4AN2-Z
C22
1)
1100 (1250)
1025
6SL3300-7TG41-3AA0
6SL3305-7TG41-0AA3
6SL3330-7TG41-0AA3
6SL3335-7TG41-0AA3
3WL1112-2BB34-4AN2-Z
C22
1)
1400 (1500)
1270
6SL3300-7TG41-3AA0
6SL3305-7TG41-3AA3
6SL3330-7TG41-3AA3
6SL3335-7TG41-3AA3
3WL1116-2BB34-4AN2-Z
C22
1)
1700 (1880)
1560
6SL3305-7TG41-6AA3
6SL3335-7TG41-6AA3
3WL1116-2BB34-4AN2-Z
C22
1)
1)
The breakers must always be switched ON and OFF by the sequence
control. An interlocking set 3WL9111-0BA21-0AA0 as described in
Catalog LV 10 should be provided for the circuit breakers in order to
exclude the risk of unintentional manual operation. Manual operation
bypasses the pre-charging circuit and can therefore destroy the Line
Module.