Assignment of line-side power components to Smart Line Modules in chassis format
Rated output
at 400 V, 50 Hz
(460 V, 60 Hz) or
690 V, 50 Hz
(575 V, 60 Hz)
Rated input
current
Suitable for
Smart Line Module
Main contactor
Fixed-mounted
circuit breaker
Switch
disconnector
without handle
and shaft
Switch
disconnector
with handle
and shaft
kW (hp)
A
6SL3330-...
Article No.
Article No.
Article No.
Article No.
Line voltage 380 ... 480 V 3 AC
250 (385)
463
6TE35-5AA3
3RT1476-6AP36
–
3KL6130-1AB02
3KL6130-1GB02
355 (545)
614
6TE37-3AA3
3RT1476-6AP36
–
3KL6230-1AB02
3KL6230-1GB02
500 (770)
883
6TE41-1AA3
–
3WL1210-4CB34-4AN2-Z
C22
1)
–
–
630 (970)
1093
6TE41-3AA3
–
3WL1212-4CB34-4AN2-Z
C22
1)
–
–
800 (1230)
1430
6TE41-7AA3
–
3WL1216-4CB34-4AN2-Z
C22
1)
–
–
Line voltage 500 ... 690 V 3 AC
450 (500)
463
6TG35-5AA3
3RT1466-6AP36
–
3KL6130-1AB02
3KL6130-1GB02
710 (790)
757
6TG38-8AA3
3RT1466-6AP36
(3 units)
–
3KL6230-1AB02
3KL6230-1GB02
1000 (1115)
1009
6TG41-2AA3
–
3WL1212-4CB34-4AN2-Z
C22
1)
–
–
1400 (1465)
1430
6TG41-7AA3
–
3WL1216-4CB34-4AN2-Z
C22
1)
–
–
Rated output
at 400 V, 50 Hz
(460 V, 60 Hz) or
690 V, 50 Hz
(575 V, 60 Hz)
Rated input
current
Suitable for
Smart Line Module
Cable protection fuse
Cable protection fuse incl.
semiconductor protection
Rated current
Rated current
kW (hp)
A
6SL3330-...
A
Article No.
A
Article No.
Line voltage 380 ... 480 V 3 AC
250 (385)
463
6TE35-5AA3
500
3NA3365
560
3NE1435-2
355 (545)
614
6TE37-3AA3
630
3NA3372
710
3NE1437-2
500 (770)
883
6TE41-1AA3
1000
3NA3480
2 × 500
3NE1334-2
(2 units)
630 (970)
1093
6TE41-3AA3
1250
3NA3482
2 × 630
3NE1436-2
(2 units)
800 (1230)
1430
6TE41-7AA3
2 × 800
3NA3475
(2 units)
2 × 850
3NE1448-2
(2 units)
Line voltage 500 ... 690 V 3 AC
450 (500)
463
6TG35-5AA3
500
3NA3365-6
560
3NE1435-2
710 (790)
757
6TG38-8AA3
2 × 400
3NA3360-6
(2 units)
850
3NE1448-2
1000 (1115)
1009
6TG41-2AA3
3 × 355
3NA3354-6
(3 units)
2 × 560
3NE1435-2
(2 units)
1400 (1465)
1430
6TG41-7AA3
3 × 500
3NA3365-6
(3 units)
2 × 850
3NE1448-2
(2 units)
1)
The breakers must always be switched ON and OFF by the sequence
control. An interlocking set 3WL9111-0BA21-0AA0 as described in
Catalog LV 10 should be provided for the circuit breakers in order to
exclude the risk of unintentional manual operation. Manual operation
bypasses the pre-charging circuit and can therefore destroy the Line
Module.
© Siemens AG 2017