SIEMENS
7/207
Siemens D 21.4 · 2017
SINAMICS S120 drive system
Chassis format
Line-side power components for chassis format
> Recommended line-side system components
7
■
Selection and ordering data
(continued)
Assignment of line-side power components to air-cooled and liquid-cooled Basic Line Modules in chassis format
Rated output
at 400 V, 50 Hz
(460 V, 60 Hz) or
690 V, 50 Hz
(575 V, 60 Hz)
Rated input
current
Suitable for
Basic Line Module
Main
contactor
Fixed-mounted
circuit breaker
Switch
disconnector
without handle
and shaft
Switch
disconnector
with handle
and shaft
kW (hp)
A
Type
Article No.
Article No.
Article No.
Line voltage 380 ... 480 V 3 AC
200 (305)
365
6SL3330-1TE34-2AA3
1)
3RT1075-...
–
3KL6130-1AB02
3KL6130-1GB02
250 (385)
460
6SL3330-1TE35-3AA3
1)
3RT1076-...
–
3KL6130-1AB02
3KL6130-1GB02
360 (555)
610
6SL3335-1TE37-4AA3
2)
3RT1076-...
–
3KL6130-1AB02
3KL6130-1GB02
400 (615)
710
6SL3330-1TE38-2AA3
1)
3RT1066-...
(3 units)
–
3KL6230-1AB02
3KL6230-1GB02
3)
560 (860)
1010
6SL3330-1TE41-2AA3
1)
–
3WL1112-2BB34-4AN2-Z
C22
4)
–
–
600 (925)
1000
6SL3335-1TE41-2AA3
2)
–
3WL1112-2BB34-4AN2-Z
C22
4)
–
–
710 (1090)
1265
6SL3330-1TE41-5AA3
1)
–
3WL1116-2BB34-4AN2-Z
C22
4)
–
–
830 (1280)
1420
6SL3335-1TE41-7AA3
2)
–
3WL1116-2BB34-4AN2-Z
C22
4)
–
–
900 (1390)
1630
6SL3330-1TE41-8AA3
1)
–
3WL1220-2BB34-4AN2-Z
C22
4)
–
–
Line voltage 500 ... 690 V 3 AC
250 (250)
260
6SL3330-1TG33-0AA3
1)
3RT1066-...
–
3KL5730-1AB01
3KL5730-1GB01
355 (350/395)
375
6SL3330-1TG34-3AA3
1)
3RT1075-…
–
3KL6130-1AB02
3KL6130-1GB02
340
6SL3335-1TG34-2AA3
2)
560 (600)
575
6SL3330-1TG36-8AA3
1)
3RT1076-…
–
3KL6130-1AB02
3KL6130-1GB02
630 (705)
600
6SL3335-1TG37-3AA3
2)
3RT1076-…
–
3KL6130-1AB02
3KL6130-1GB02
900 (900)
925
6SL3330-1TG41-1AA3
1)
–
3WL1210-4BB34-4AN2-Z
C22
4)
–
–
1100 (1250/1230)
1180
6SL3330-1TG41-4AA3
1)
–
3WL1212-4BB34-4AN2-Z
C22
4)
–
–
1070
6SL3335-1TG41-3AA3
2)
1370 (1530)
1350
6SL3335-1TG41-7AA3
2)
–
3WL1216-4BB34-4AN2-Z
C22
4)
–
–
1500 (1500)
1580
6SL3330-1TG41-8AA3
1)
–
3WL1220-4BB34-4AN2-Z
C22
4)
–
–
1)
6SL3330-… is the air-cooled version.
2)
6SL3335-… is the liquid-cooled version.
3)
Suitable only for 3NE1 fuses up to size 3.
4)
The breakers must always be switched ON and OFF by the sequence
control. An interlocking set 3WL9111-0BA21-0AA0 as described in
Catalog LV 10 should be provided for the circuit breakers in order to
exclude the risk of unintentional manual operation. Manual operation
bypasses the pre-charging circuit and can therefore destroy the Line
Module.
© Siemens AG 2017