SIEMENS
7/201
Siemens D 21.4 · 2017
SINAMICS S120 drive system
Chassis format
Line-side power components for chassis format
> Line filters
7
■
Technical specifications
(continued)
Line voltage 380 ... 480 V 3 AC
Line filter
6SL3000-0BE33-1AA0
6SL3000-0BE35-0AA0
6SL3760-0MB00-0AA0
6SL3760-0MC00-0AA0
Rated current
A
400
600
840
1405
Power loss
1)
At 50 Hz
kW
0.042
0.06
0.058
0.111
Load/line supply connection
M10 connecting lugs
M10 connecting lugs
M10 connecting lugs
M10 connecting lugs
PE connection
Hole for M8
Hole for M10
Hole for M10
Hole for M10
Degree of protection
IP00
IP00
IP00
IP00
Dimensions
• Width
mm (in)
360 (14.2)
390 (15.3)
425 (16.7)
505 (19.9)
• Height
mm (in)
240 (9.45)
265 (10.4)
265 (10.4)
265 (10.4)
• Depth
mm (in)
116 (4.57)
140 (5.51)
145 (5.71)
145 (5.71)
Weight, approx.
kg (lb)
12.7 (28)
19.9 (44)
25.9 (57)
28.9 (64)
Suitable for Smart Line Module in chassis format
• Air-cooled
6SL3330-...
–
6TE35-5AA3
6TE37-3AA3
6TE41-1AA3
6TE41-3AA3
6TE41-7AA3
Suitable for Active Line Module in chassis format
• Air-cooled
6SL3330-...
7TE32-1AA3
7TE32-6AA3
7TE33-8AA3
7TE35-0AA3
7TE36-1AA3
7TE37-5AA3
7TE38-4AA3
7TE41-0AA3
7TE41-2AA3
7TE41-4AA3
Line voltage 500 ... 690 V 3 AC
Line filter
6SL3760-0ME00-0AA0
6SL3760-0MN00-0AA0
6SL3760-0MG00-0AA0
Rated current
A
600
1025
1270
Power loss
1)
At 50 Hz
kW
0.063
0.063
0.097
Load/line supply connection
M10 connecting lugs
M12 connecting lugs
M12 connecting lugs
PE connection
Hole for M10
Hole for M10
Hole for M10
Degree of protection
IP00
IP00
IP00
Dimensions
• Width
mm (in)
400 (15.7)
425 (16.7)
505 (19.9)
• Height
mm (in)
365 (14.4)
365 (14.4)
365 (14.4)
• Depth
mm (in)
140 (5.51)
145 (5.71)
145 (5.71)
Weight, approx.
kg (lb)
27 (60)
36.7 (81)
36.7 (81)
Suitable for Smart Line Module in chassis format
• Air-cooled
6SL3330-...
6TG35-5AA3
6TG38-8AA3
6TG41-2AA3
6TG41-7AA3
Suitable for Active Line Module in chassis format
• Air-cooled
6SL3330-...
7TG35-8AA3
7TG37-4AA3
7TG41-0AA3
7TG41-3AA3
1)
The specified power loss represents the maximum value at 100 %
utilization. The value is lower under normal operating conditions.
© Siemens AG 2017