SIEMENS
7/195
Siemens D 21.4 · 2017
SINAMICS S120 drive system
Chassis format
Liquid-cooled Motor Modules in chassis format
7
■
Technical specifications
(continued)
Line voltage 500 ... 690 V 3 AC
DC link voltage 675 ... 1035 V DC
Motor Modules
6SL3325-
1TG37-4AA3
6SL3325-
1TG38-0AA3
1)
6SL3325-
1TG38-1AA3
6SL3325-
1TG41-0AA3
6SL3325-
1TG41-3AA3
6SL3325-
1TG41-6AA3
Type rating
• At
I
L
(50 Hz 690 V)
2)
kW
710
800
800
1000
1200
1500
• At
I
H
(50 Hz 690 V)
2)
kW
630
710
710
900
1000
1260
• At
I
L
(50 Hz 500 V)
2)
kW
500
560
560
710
900
1000
• At
I
H
(50 Hz 500 V)
2)
kW
450
500
560
630
800
900
• At
I
L
(60 Hz 575 V)
3)
hp
700
800
800
1000
1250
1500
• At
I
H
(60 Hz 575 V)
3)
hp
700
700
700
900
1000
1250
Output current
• Rated current
I
rated O
A
735
810
810
1025
1270
1560
• Base-load current
I
L
5)
A
710
790
790
1000
1230
1500
• Base-load current
I
H
5)
A
657
724
724
917
1136
1284
• Maximum current
I
max O
A
1065
1185
1185
1500
1845
2055
DC link current
• Rated current
I
rated DC
when supplied via
-
Basic Line Module
A
903
990
990
1250
1550
1903
-
Active Line Module
A
759
891
891
1125
1395
1605
• Base-load current
I
L DC
4)
when supplied from
-
Basic Line Module
A
870
948
963
1219
1500
1800
-
Active Line Module
A
781
870
869
1100
1353
1650
• Base-load current
I
H DC
5)
when supplied from
-
Basic Line Module
A
795
885
883
1118
1384
1680
-
Active Line Module
A
732
808
796
1009
1250
1550
Current demand
• 24 V DC auxiliary power supply
A
1.6
1.6
1.46
1.46
1.46
1.46
DC link capacitance
μ
F
10500
10500
14000
16000
19330
21000
Pulse frequency
6)
• Rated frequency
kHz
1.25
1.25
1.25
1.25
1.25
1.25
• Pulse frequency, max.
-
Without current derating
kHz
1.25
1.25
1.25
1.25
1.25
1.25
-
With current derating
kHz
7.5
7.5
7.5
7.5
7.5
7.5
Power loss, max.
6)
• At 50 Hz 690 V
kW
7.65
8.47
9.56
10.87
13.49
17.9
• At 60 Hz 575 V
kW
6.67
7.39
8.34
9.55
11.84
15.7
• Dissipated to ambient air
kW
0.2
0.22
0.43
0.53
0.57
0.78
Coolant volume flow
8)
l/min
16
16
27
27
27
27
Liquid volume
of the integrated heat exchanger
dm
3
0.74
0.74
1.56
1.56
1.56
1.56
Pressure drop, typ.
9)
for volume flow
Pa
70000
70000
70000
70000
70000
70000
Heat exchanger material
Aluminum
Aluminum
Aluminum
Aluminum
Aluminum
Aluminum
Sound pressure level
L
pA
(1 m) at 50/60 Hz
dB
54
54
56
56
56
56
DC link connection
DCP, DCN
2 × hole for M12
Busbar
2 × hole for M12
Busbar
2 × hole for M12
Busbar
2 × hole for M12
Busbar
2 × hole for M12
Busbar
2 × hole for M12
Busbar
Motor connection
U2, V2, W2
2 × hole for M12
2 × hole for M12
2 × hole for M12
2 × hole for M12
2 × hole for M12
2 × hole for M12
• Conductor cross section, max. (IEC)
mm
2
4 × 185
4 x 185
Busbar
Busbar
Busbar
Busbar
PE/GND connection
2 × hole for M12
2 × hole for M12
2 × hole for M12
2 × hole for M12
2 × hole for M12
2 × hole for M12
• Conductor cross section, max. (IEC)
mm
2
4 × 185
4 × 185
Busbar
Busbar
Busbar
Busbar
Footnotes see next page.
© Siemens AG 2017