7/194
Siemens D 21.4 · 2017
SINAMICS S120 drive system
Chassis format
Liquid-cooled Motor Modules in chassis format
7
Cable length, max.
9)
• Shielded
m (ft)
300 (984)
300 (984)
300 (984)
300 (984)
300 (984)
300 (984)
• Unshielded
m (ft)
450 (1476)
450 (1476)
450 (1476)
450 (1476)
450 (1476)
450 (1476)
Dimensions
• Width
mm (in)
150 (5.91)
150 (5.91)
150 (5.91)
150 (5.91)
265 (10.4)
265 (10.4)
• Height
mm (in)
728 (28.7)
728 (28.7)
1172 (46.1)
1172 (46.1)
1002 (39.5)
1002 (39.5)
• Depth
mm (in)
545 (21.5)
545 (21.5)
545 (21.5)
545 (21.5)
545 (21.5)
545 (21.5)
Weight, approx.
kg (lb)
41 (90)
41 (90)
80 (176)
80 (176)
110 (243)
110 (243)
Frame size
FXL
FXL
GXL
GXL
HXL
HXL
Line voltage 500 ... 690 V 3 AC
DC link voltage 675 ... 1035 V DC
Motor Modules
6SL3325-
1TG31-0AA3
6SL3325-
1TG31-5AA3
6SL3325-
1TG32-2AA3
6SL3325-
1TG33-3AA3
6SL3325-
1TG34-7AA3
6SL3325-
1TG35-8AA3
1)
Rated output of a typical 6-pole standard induction motor based on
I
L
or
I
H
for 500 V or 690 V 3 AC 50 Hz.
2)
Rated output of a typical 6-pole standard induction motor based on
I
L
or
I
H
for 575 V 3 AC 60 Hz.
3)
The base-load current
I
L
is based on a duty cycle of 110 % for 60 s or
150 % for 10 s with a duty cycle duration of 300 s.
4)
The base-load current
I
H
is based on a duty cycle of 150 % for 60 s or
160 % for 10 s with a duty cycle duration of 300 s.
5)
Additional notes regarding the correlation between the pulse frequency
and maximum output current/output frequency is provided in the
SINAMICS Low Voltage Engineering Manual.
6)
The specified power loss represents the maximum value at 100 % utilization.
The value is lower under normal operating conditions. To ensure safe dissi-
pation of the minor power loss released to the ambient air, it is important to
follow the instructions pertaining to control cabinet installation in the
SINAMICS Low Voltage Engineering Manual.
7)
The value applies to coolants comprising water and a mixture of water and
anti-freeze agent.
8)
The value is valid for water as coolant.
Additional information and notes on other coolants is provided in the
SINAMICS Low Voltage Engineering Manual.
9)
Total of all motor cables. Longer cable lengths for specific configurations
are available on request.
For additional information, please refer to the SINAMICS Low Voltage.
■
Technical specifications