SIEMENS
7/185
Siemens D 21.4 · 2017
SINAMICS S120 drive system
Chassis format
Liquid-cooled Basic Line Modules in chassis format
7
■
Technical specifications
(continued)
Line voltage 380 ... 480 V 3 AC
Basic Line Modules
6SL3335-1TE37-4AA3
6SL3335-1TE41-2AA3
6SL3335-1TE41-7AA3
Rated power
• At
I
rated DC
(50 Hz 400 V)
kW
360
600
830
• At
I
H
(50 Hz 400 V)
kW
280
450
650
• At
I
rated DC
(60 Hz 460 V)
hp
555
925
1280
• At
I
H
(60 Hz 460 V)
hp
430
690
1000
DC link current
• Rated current
I
rated DC
A
740
1220
1730
• Base-load current
I
H DC
1)
A
578
936
1350
• Maximum current
I
max DC
A
1110
1830
2595
Input current
• Rated current
I
rated I
A
610
1000
1420
• Maximum current
I
max I
A
915
1500
2130
Current demand
• 24 V DC auxiliary power supply
A
0.7
0.7
0.7
DC link capacitance
• Basic Line Module
μ
F
12000
20300
26100
• Drive line-up, max.
μ
F
96000
162400
208800
Power loss, at
50 Hz 400 V
2)
• Dissipated to coolant
kW
2.7
4.36
5.82
• Dissipated to ambient air
kW
0.25
0.41
0.57
• Total
kW
2.95
4.77
6.39
Coolant volume flow
3)
l/min
9
9
12
Liquid volume
of the integrated heat exchanger
dm
3
0.45
0.45
0.79
Pressure drop, typ.
4)
for volume flow
Pa
70000
70000
70000
Heat exchanger material
Aluminum
Aluminum
Aluminum
Sound pressure level
L
pA
(1 m) at 50/60 Hz
dB
54
56
56
Line connection
U1, V1, W1
2 × M12 nut
2 × M12 nut
2 × M12 nut
• Conductor cross section, max. (IEC)
mm
2
4 × 240
4 × 240
4 × 240
DC link connection
DCP, DCN
2 × M12 nut
Busbar
2 × M12 nut
Busbar
2 × M12 nut
Busbar
PE/GND connection
2 × M12 nut
2 × M12 nut
2 × M12 nut
• Conductor cross section, max. (IEC)
mm
2
4 × 240
4 × 240
4 × 240
Cable length, max.
5)
• Shielded
m (ft)
2600 (8531)
4000 (13124)
4800 (15749)
• Unshielded
m (ft)
3900 (12796)
6000 (19686)
7200 (23623)
Dimensions
• Width
mm (in)
160 (6.3)
160 (6.3)
160 (6.3)
• Height
mm (in)
1137 (44.8)
1137 (44.8)
1562 (61.5)
• Depth
mm (in)
545 (21.5)
545 (21.5)
545 (21.5)
Weight, approx.
kg (lb)
108 (238)
108 (238)
185 (408)
Frame size
FBL
FBL
GBL
Minimum short-circuit current
6)
A
8800
12400
20000
1)
The base-load current
I
H DC
is the basis for a duty cycle of 150 % for 60 s
or
I
max DC
for 5 s with a duty cycle duration of 300 s.
2)
The specified power loss represents the maximum value at 100 % utilization.
The value is lower under normal operating conditions. To ensure safe dissi-
pation of the minor power loss released to the ambient air, it is important to
follow the instructions pertaining to control cabinet installation in the
SINAMICS Low Voltage Engineering Manual.
3)
The value applies to coolants comprising water and a mixture of water and
anti-freeze agent.
4)
The value is valid for water as coolant.
Additional information and notes on
other coolants is provided in the SINAMICS Low Voltage Engineering
Manual
.
5)
Total of all motor cables and DC link. Longer cable lengths for specific
configurations are available on request.
For additional information, please
refer to the SINAMICS Low Voltage Engineering Manual
.
6)
Current required for reliably triggering protective devices.
© Siemens AG 2017