SIEMENS
7/178
Siemens D 21.4 · 2017
SINAMICS S120 drive system
Chassis format
Liquid-cooled Active Line Modules in chassis format
7
■
Technical specifications
(continued)
Line voltage 500 ... 690 V 3 AC
Active Line Modules
6SL3335-
7TG35-8AA3
6SL3335-
7TG37-4AA3
6SL3335-
7TG38-1AA3
6SL3335-
7TG41-0AA3
6SL3335-
7TG41-3AA3
6SL3335-
7TG41-6AA3
Rated power
• At
I
rated DC
(50 Hz 690 V)
kW
630
800
900
1100
1400
1700
• At
I
H DC
(50 Hz 690 V)
kW
620
705
670
1000
1215
1490
• At
I
rated DC
(50 Hz 500 V)
kW
447
560
620
780
965
1180
• At
I
H DC
(50 Hz 500 V)
kW
450
510
485
710
880
1080
• At
I
rated DC
(60 Hz 575 V)
hp
675
900
975
1250
1500
1880
• At
I
H DC
(60 Hz 575 V)
hp
506
600
765
1000
1250
1530
DC link current
• Rated current
I
rated DC
A
644
823
907
1147
1422
1740
• Base-load current
I
H DC
1)
A
573
732
808
1022
1266
1550
• Maximum current
I
max DC
A
966
1235
1360
1722
2133
2620
Infeed/regenerative feedback current
• Rated current
I
rated I
A
575
735
810
1025
1270
1560
• Maximum current
I
max I
A
862
1100
1214
1537
1905
2055
Current demand
• 24 V DC auxiliary power supply
A
1.6
1.6
1.6
1.6
1.46
1.5
DC link capacitance
• Active Line Module
μ
F
9670
10500
10500
19330
19330
21000
Pulse frequency
kHz
2.5
2.5
2.5
2.5
2.5
2.5
Power loss, at 50 Hz 690 V
2)
• Dissipated to coolant
kW
5.45
7.45
8.28
10.37
12.98
17.17
• Dissipated to ambient air
kW
0.16
0.2
0.22
0.53
0.57
0.79
• Total
kW
5.61
7.65
8.5
10.9
13.55
17.96
Coolant volume flow
3)
l/min
16
16
16
27
27
27
Liquid volume
of the integrated heat exchanger
dm
3
0.74
0.74
0.74
1.56
1.56
1.56
Pressure drop, typ.
4)
for volume flow
Pa
70000
70000
70000
70000
70000
70000
Heat exchanger material
Aluminum
Aluminum
Aluminum
Aluminum
Aluminum
Aluminum
Sound pressure level
L
pA
5)
(1 m) at 50/60 Hz
dB
70/73
71/73
71/73
71/73
71/73
71/73
Line connection
U1, V1, W1
2 × hole for M12
2 × hole for M12
2 × hole for M12
2 × hole for M12
2 × hole for M12
2 × hole for M12
• Conductor cross section, max. (IEC)
mm
2
4 × 185
4 × 185
4 × 185
Busbar
Busbar
Busbar
DC link connection
DCP, DCN
2 × hole for M12
Busbar
2 × hole for M12
Busbar
2 × hole for M12
Busbar
2 × hole for M12
Busbar
2 × hole for M12
Busbar
2 × hole for M12
Busbar
PE/GND connection
2 × hole for M12
2 × hole for M12
2 × hole for M12
2 × hole for M12
2 × hole for M12
2 × hole for M12
• Conductor cross section, max. (IEC)
mm
2
4 × 185
4 × 185
4 × 185
Busbar
Busbar
Busbar
Cable length, max.
6)
• Shielded
m (ft)
2250 (7382)
2250 (7382)
2250 (7382)
2250 (7382)
2250 (7382)
2250 (7382)
• Unshielded
m (ft)
3375 (11073)
3375 (11073)
3375 (11073)
3375 (11073)
3375 (11073)
3375 (11073)
Dimensions
• Width
mm (in)
265 (10.4)
265 (10.4)
265 (10.4)
295 (11.6)
295 (11.6)
295 (11.6)
• Height
mm (in)
1002 (39.4)
1002 (39.4)
1002 (39.4)
1516 (59.7)
1516 (59.7)
1516 (59.7)
• Depth
mm (in)
545 (21.5)
545 (21.5)
545 (21.5)
545 (21.5)
545 (21.5)
545 (21.5)
Weight, approx.
kg (lb)
110 (243)
110 (243)
110 (243)
220 (486)
220 (486)
230 (507)
Frame size
HXL
HXL
HXL
JXL
JXL
JXL
Minimum short-circuit current
7)
A
8400
10500
12600
16000
20000
24000
1)
The base-load current
I
H DC
is the basis for a duty cycle of 150 % for 60 s
or
I
max DC
for 5 s with a duty cycle duration of 300 s.
2)
The specified power loss represents the maximum value at 100 % utilization.
The value is lower under normal operating conditions. To ensure safe dissi-
pation of the minor power loss released to the ambient air, it is important to
follow the instructions pertaining to control cabinet installation in the
SINAMICS Low Voltage Engineering Manual.
3)
The value applies to coolants comprising water and a mixture of water and
anti-freeze agent.
4)
The value is valid for water as coolant.
Additional information and notes on
other coolants is provided in the SINAMICS Low Voltage Engineering
Manual
.
5)
Total sound pressure level of Active Interface Module and Active Line
Module.
6)
Total of all motor cables and DC link. Longer cable lengths for specific
configurations are available on request.
For additional information, please
refer to the SINAMICS Low Voltage Engineering Manual.
7)
Current required for reliably triggering protective devices.
© Siemens AG 2017