SINAMICS S120 drive system
Chassis format
Liquid-cooled Power Modules in chassis format
7
■
Technical specifications
(continued)
Line voltage 380 V... 480 V 3 AC
Power Modules
6SL3315-1TE32-1AA3
6SL3315-1TE32-6AA3
6SL3315-1TE33-1AA3
6SL3315-1TE35-0AA3
Type rating
• At
I
L
(50 Hz 400 V)
1)
kW
110
132
160
250
• At
I
H
(50 Hz 400 V)
1)
kW
90
110
132
200
• At
I
L
(60 Hz 460 V)
2)
hp
150
200
250
400
• At
I
H
(60 Hz 460 V)
2)
hp
150
200
200
350
Output current
• Rated current
I
rated O
A
210
260
310
490
• Base-load current
I
L
3)
A
205
250
302
477
• Base-load current
I
H
4)
A
178
233
277
438
• Max. output current
I
max O
A
307
375
453
715
Input current
• Rated current
I
rated I
A
230
285
340
540
• Maximum current
I
max I
A
336
411
496
788
Current demand
• 24 V DC auxiliary power supply
A
1.4
1.4
1.5
1.5
Pulse frequency
5)
• Rated frequency
kHz
2
2
2
2
• Pulse frequency, max.
-
Without current derating
kHz
2
2
2
2
-
With current derating
kHz
8
8
8
8
Power loss, at 50 Hz 400 V
6)
• Dissipated to coolant
kW
2.36
2.97
3.31
5.29
• Dissipated to ambient air
kW
0.06
0.07
0.09
0.14
• Total
kW
2.42
3.04
3.4
5.43
Coolant volume flow
7)
l/min
9
9
12
12
Liquid volume
of the integrated heat exchanger
dm
3
0.52
0.52
0.88
0.88
Pressure drop, typ.
8)
for volume flow
Pa
70000
70000
70000
70000
Heat exchanger material
Stainless steel
Stainless steel
Stainless steel
Stainless steel
Sound pressure level
L
pA
(1 m) at 50/60 Hz
dB
52
52
52
52
Line connection
U1, V1, W1
Hole for M12
Hole for M12
Hole for M12
Hole for M12
• Conductor cross section, max. (IEC)
mm
2
2 × 95
2 × 95
2 × 240
2 × 240
DC link connection
DCP, DCN
Hole for M12
Hole for M12
Hole for M12
Hole for M12
• Conductor cross section, max. (IEC)
mm
2
2 × 95
2 × 95
2 × 240
2 × 240
Motor connection
U2/T1, V2/T2, W2/T3
Hole for M12
Hole for M12
2 × hole for M12
2 × hole for M12
• Conductor cross section, max. (IEC)
mm
2
2 × 95
2 × 95
2 × 240
2 × 240
Cable length, max.
9)
• Shielded
m (ft)
300 (984)
300 (984)
300 (984)
300 (984)
• Unshielded
m (ft)
450 (1476)
450 (1476)
450 (1476)
450 (1476)
PE/GND connection
2 × hole for M12
2 × hole for M12
2 × hole for M12
2 × hole for M12
• Conductor cross section, max. (IEC)
mm
2
2 × 95
2 × 95
2 × 240
2 × 240
Dimensions
• Width
mm (in)
265 (10.4)
265 (10.4)
265 (10.4)
265 (10.4)
• Height
mm (in)
836 (32.9)
836 (32.9)
983 (38.7)
983 (38.7)
• Depth
mm (in)
549 (21.6)
549 (21.6)
549 (21.6)
549 (21.6)
Weight, approx.
kg (lb)
77 (170)
77 (170)
108 (238)
108 (238)
Frame size
FL
FL
GL
GL
Minimum short-circuit current
10)
A
3000
3600
4400
8000
1)
Rated output of a typical 6-pole standard induction motor based on
I
L
or
I
H
for 3 AC 50 Hz 400 V.
2)
Rated output of a typical 6-pole standard induction motor based on
I
L
or
I
H
for 3 AC 60 Hz 460 V.
3)
The base-load current
I
L
is based on a duty cycle of 110 % for 60 s or
150 % for 10 s with a duty cycle duration of 300 s.
4)
The base-load current
I
H
is based on a duty cycle of 150 % for 60 s or
160 % for 10 s with a duty cycle duration of 300 s.
5)
Information regarding the correlation between the pulse frequency and
maximum output current/output frequency is provided in the
SINAMICS Low Voltage Engineering Manual.
6)
The specified power loss represents the maximum value at 100 % utilization.
The value is lower under normal operating conditions. To ensure safe dissi-
pation of the minor power loss released to the ambient air, it is important to
follow the instructions pertaining to control cabinet installation in the
SINAMICS Low Voltage Engineering Manual.
7)
The value applies to coolants comprising water and a mixture of water and
anti-freeze agent.
8)
The value is valid for water as coolant.
Additional information and notes on
other coolants is provided in the SINAMICS Low Voltage Engineering
Manual
.
9)
Longer cable lengths for specific configurations are available on request.
For additional information, please refer to the SINAMICS Low Voltage
Engineering Manual
.
10)
Current required for reliably triggering protective devices.