SIEMENS
7/160
Siemens D 21.4 · 2017
SINAMICS S120 drive system
Chassis format
Air-cooled Motor Modules in chassis format
7
■
Technical specifications
(continued)
Line voltage 500 ... 690 V 3 AC
DC link voltage 675 ... 1035 V DC
Motor Modules
6SL3320-1TG38-1AA3
6SL3320-1TG38-8AA3
6SL3320-1TG41-0AA3
6SL3320-1TG41-3AA3
Type rating
• At
I
L
(50 Hz 690 V)
1)
kW
800
900
1000
1200
• At
I
H
(50 Hz 690 V)
1)
kW
710
800
900
1000
• At
I
L
(50 Hz 500 V)
1)
kW
560
630
710
900
• At
I
H
(50 Hz 500 V)
1)
kW
500
560
630
800
• At
I
L
(60 Hz 575 V)
2)
hp
800
900
1000
1250
• At
I
H
(60 Hz 575 V)
2)
hp
700
800
900
1000
Output current
• Rated current
I
rated O
A
810
910
1025
1270
• Base-load current
I
L
3)
A
790
880
1000
1230
• Base-load current
I
H
4)
A
724
814
917
1136
• Maximum current
I
max A
A
1185
1320
1500
1845
DC link current
• Rated current
I
rated DC
when supplied via
-
Basic/Smart Line Module
A
972
1092
1230
1524
-
Active Line Module
A
875
983
1107
1372
• Base-load current
I
L DC
3)
when supplied via
-
Basic/Smart Line Module
A
947
1064
1199
1485
-
Active Line Module
A
853
958
1079
1337
• Base-load current
I
H DC
4)
when supplied via
-
Basic/Smart Line Module
A
865
971
1094
1356
-
Active Line Module
A
778
874
985
1221
Current demand
• 24 V DC auxiliary power supply
A
1.25
1.4
1.4
1.4
• 500 V AC
A
4.4
4.4
4.4
4.4
• 690 V AC
A
3.1
3.1
3.1
3.1
DC link capacitance
μ
F
11100
14400
14400
19200
Pulse frequency
5)
• Rated frequency
kHz
1.25
1.25
1.25
1.25
• Pulse frequency, max.
-
Without current derating
kHz
1.25
1.25
1.25
1.25
-
With current derating
kHz
7.5
7.5
7.5
7.5
Power loss, max.
6)
• At 50 Hz 690 V
kW
11.5
11.7
13.2
16.0
• At 60 Hz 575 V
kW
10.5
10.6
12.0
14.2
Cooling air requirement
m
3
/s (ft
3
/s)
1.08 (38.1)
1.08 (38.1)
1.08 (38.1)
1.08 (38.1)
Sound pressure level
L
pA
(1 m) at 50/60 Hz
dB
71/73
71/73
71/73
71/73
DC link connection
DCP, DCN
4 × hole for M10
Busbar
4 × hole for M10
Busbar
4 × hole for M10
Busbar
4 × hole for M10
Busbar
Connection for Braking Module
DCPA, DCNA
7)
M8 stud
M8 stud
M8 stud
M8 stud
Connection for dv/dt filter
DCPS, DCNS
2 x M10 screw
2 x M10 screw
2 x M10 screw
2 x M10 screw
• Conductor cross section, max. (IEC)
mm
2
2 × 185
2 × 185
2 × 185
2 × 185
Motor connection
U2, V2, W2
3 × M12 screw
3 × M12 screw
3 × M12 screw
3 × M12 screw
• Conductor cross section, max. (IEC)
mm
2
6 × 240
6 × 240
6 × 240
6 × 240
Footnotes see next page.
© Siemens AG 2017