SINAMICS S120 drive system
Chassis format
Air-cooled Motor Modules in chassis format
7
PE1/GND connection
M12 screw
M12 screw
M12 screw
• Conductor cross section, max. (IEC)
mm
2
240
240
240
PE2/GND connection
2 × M12 screw
2 × M12 screw
2 × M12 screw
• Conductor cross section, max. (IEC)
mm
2
2 × 240
2 × 240
2 × 240
Degree of protection
IP00
IP00
IP00
Dimensions
• Width
mm (in)
503 (19.8)
503 (19.8)
503 (19.8)
• Height
mm (in)
1475 (58.1)
1475 (58.1)
1475 (58.1)
• Depth
mm (in)
547 (21.5)
547 (21.5)
547 (21.5)
Weight, approx.
kg (lb)
290 (639)
290 (639)
290 (639)
Frame size
HX
HX
HX
Line voltage 380 ... 480 V 3 AC
DC link voltage 510 ... 720 V DC
Motor Modules
6SL3320-1TE36-1AA3
6SL3320-1TE37-5AA3
6SL3320-1TE38-4AA3
1)
Rated output of a typical 6-pole standard induction motor based on
I
L
or
I
H
for 400 V 3 AC 50 Hz.
2)
Rated output of a typical 6-pole standard induction motor based on
I
L
or
I
H
for 460 V 3 AC 60 Hz.
3)
The base-load current
I
L
is based on a duty cycle of 110 % for 60 s or
150 % for 10 s with a duty cycle duration of 300 s.
4)
The base-load current
I
H
is based on a duty cycle of 150 % for 60 s or
160 % for 10 s with a duty cycle duration of 300 s.
5)
Information regarding the correlation between the pulse frequency and
maximum output current/output frequency is provided in the
SINAMICS Low Voltage Engineering Manual
.
6)
The specified power loss represents the maximum value at 100 % utilization.
The value is lower under normal operating conditions.
7)
The connecting cables are included in the scope of supply of the Braking
Module.
8)
Total of all motor cables and DC link. Longer cable lengths for specific
configurations are available on request.
For additional information, please
refer to the SINAMICS Low Voltage Engineering Manual
.
■
Technical specifications