SIEMENS
7/144
Siemens D 21.4 · 2017
SINAMICS S120 drive system
Chassis format
Air-cooled Basic Line Modules in chassis format
7
■
Technical specifications
(continued)
Line voltage 500 ... 690 V 3 AC
Basic Line Modules
6SL3330-
1TG33-0AA3
6SL3330-
1TG34-3AA3
6SL3330-
1TG36-8AA3
6SL3330-
1TG41-1AA3
6SL3330-
1TG41-4AA3
6SL3330-
1TG41-8AA3
Rated power
• At
I
rated DC
(50 Hz 690 V)
kW
250
355
560
900
1100
1500
• At
I
H DC
(50 Hz 690 V)
kW
195
280
440
710
910
1220
• At
I
rated DC
(50 Hz 500 V)
kW
175
250
390
635
810
1085
• At
I
H DC
(50 Hz 500 V)
kW
165
235
365
595
755
1015
• At
I
rated DC
(60 Hz 575 V)
hp
250
350
600
900
1250
1500
• At
I
H DC
(60 Hz 575 V)
hp
200
300
450
800
1000
1250
DC link current
• Rated current
I
rated DC
A
300
430
680
1100
1400
1880
• Base-load current
I
H DC
1)
A
234
335
530
858
1092
1467
• Maximum current
I
max DC
A
450
645
1020
1650
2100
2820
Input current
• Rated current
I
rated I
A
260
375
575
925
1180
1580
• Maximum current
I
max I
A
390
563
863
1388
1770
2370
• Max. pre-charging current (max. 3 s)
A
Internal
Internal
Internal
Internal
Internal
234
Current demand
• 24 V DC auxiliary power supply
A
1.1
1.1
1.1
1.1
1.1
1.1
DC link capacitance
• Basic Line Module
μ
F
3200
4800
7300
11600
15470
19500
• Drive line-up, max.
μ
F
25600
38400
58400
92800
123760
78000/156000
2)
Power loss, max.
3)
• At 50 Hz 690 V
kW
1.5
2.1
3.0
5.4
5.8
7.3
• At 60 Hz 575 V
kW
1.5
2.1
3.0
5.4
5.8
7.3
Cooling air requirement
m
3
/s (ft
3
/s)
0.17 (6.00)
0.17 (6.00)
0.17 (6.00)
0.36 (12.7)
0.36 (12.7)
0.36 (12.7)
Sound pressure level
L
pA
(1 m) at 50/60 Hz
dB
66/68
66/68
66/68
71/73
71/73
71/73
Line connection
U1, V1, W1
Flat connector
for M10 screw
Flat connector
for M10 screw
Flat connector
for M10 screw
Flat connector
for M12 screw
Flat connector
for M12 screw
Flat connector
for M12 screw
• Conductor cross section, max. (IEC)
mm
2
2 × 240
2 × 240
2 × 240
6 × 185
6 × 185
6 × 185
DC link connection
DCP, DCN
M10 screw
M10 screw
M10 screw
3 × hole for
M12
3 × hole for
M12
3 × hole for
M12
• Conductor cross section, max. (IEC)
mm
2
2 × 240
2 × 240
2 × 240
6 ×185
6 × 185
6 × 185
PE/GND connection
2 × hole for
M10
2 × hole for
M10
2 × hole for
M10
2 × hole for
M12
2 × hole for
M12
2 × hole for
M12
• Conductor cross section, max. (IEC)
mm
2
2 × 240
2 × 240
2 × 240
4 × 240
4 × 240
4 × 240
Cable length, max.
4)
• Shielded
m (ft)
1500 (4921)
1500 (4921)
1500 (4921)
2250 (7382)
2250 (7382)
2750 (9023)
• Unshielded
m (ft)
2250 (7382)
2250 (7382)
2250 (7382)
3375 (11073)
3375 (11073)
4125 (13534)
Degree of protection
IP00
IP00
IP00
IP00
IP00
IP00
Dimensions
• Width
mm (in)
310 (12.2)
310 (12.2)
310 (12.2)
310 (12.2)
310 (12.2)
310 (12.2)
• Height
mm (in)
1164 (45.8)
1164 (45.8)
1164 (45.8)
1653 (65.1)
1653 (65.1)
1653 (65.1)
• Depth
mm (in)
352 (13.9)
352 (13.9)
352 (13.9)
550 (21.6)
550 (21.6)
550 (21.6)
Weight, approx.
kg (lb)
96 (212)
96 (212)
96 (212)
214 (472)
214 (472)
214 (472)
Frame size
FB
FB
FB
GB
GB
GD
Minimum short-circuit current
5)
A
3000
4400
8000
10400
16000
18600
1)
The base-load current
I
H DC
is the basis for a duty cycle of 150 % for 60 s
or
I
max DC
for 5 s with a duty cycle duration of 300 s.
2)
The first value applies for one pre-charging resistor for each phase, the
second value for two precharging resistors connected in parallel for each
phase.
3)
The specified power loss represents the maximum value at 100 % utilization.
The value is lower under normal operating conditions.
4)
Total of all motor cables and DC link. Longer cable lengths for specific
configurations are available on request.
For additional information, please
refer to the SINAMICS Low Voltage Engineering Manual
.
5)
Current required for reliably triggering protective devices.
© Siemens AG 2017