SIEMENS
7/133
Siemens D 21.4 · 2017
SINAMICS S120 drive system
Chassis format
Air-cooled Active Interface Modules in chassis format
7
■
Technical specifications
(continued)
Line voltage 380 ... 480 V 3 AC
Active Interface Modules
6SL3300-7TE38-4AA0
6SL3300-7TE41-4AA0
Suitable for Active Line Module
• Rated power at 400 V
kW
380
450/500
630
800/900
- Air-cooled
6SL3330-7TE36-1AA3
6SL3330-7TE37-5AA3
6SL3330-7TE38-4AA3
6SL3330-7TE41-0AA3
6SL3330-7TE41-2AA3
6SL3330-7TE41-4AA3
- Liquid-cooled
6SL3335-7TE36-1AA3
6SL3335-7TE38-4AA3
–
–
Rated current
A
605
745/840
985
1260/1405
Bypass contactor
3RT1476-6AP36
3WL1110-2BB34-4AN2-Z
Z = C22
1)
3WL1112-2BB34-4AN2-Z
Z = C22
1)
3WL1116-2BB34-4AN2-Z
Z = C22
1)
Current demand
• 24 V DC auxiliary power supply
A
0.17
0.17
0.17
0.17
• 230 V 2 AC
-
Inrush current
A
9.9
9.9
10.5
10.5
-
Holding current
A
4.6
4.6
4.9
4.9
DC link capacitance
of the drive line-up, max.
2)
μ
F
134400
134400
230400
230400
Power loss, max.
3)
• At 50 Hz 400 V
kW
5.5
6.1
7.5
8.5
• At 60 Hz 460 V
kW
5.5
6.1
7.5
8.5
Cooling air requirement
m
3
/s (ft
3
/s)
0.4 (14.1)
0.4 (14.1)
0.4 (14.1)
0.4 (14.1)
Line/load connection
L1, L2, L3 / U2, V2, W2
4 × hole for M12
4 × hole for M12
3 × hole for M12
3 × hole for M12
• Conductor cross section, max. (IEC)
mm
2
4 × 240
4 × 240
6 × 240
6 × 240
PE/GND connection
2 × M12 nut
2 × M12 nut
4 × M12 nut
4 × M12 nut
• Conductor cross section, max. (IEC)
mm
2
2 × 240
2 × 240
4 × 240
4 × 240
Degree of protection
IP00
IP00
IP00
IP00
Dimensions
• Width
mm (in)
305 (12.0)
305 (12.0)
505 (19.9)
505 (19.9)
• Height
mm (in)
1750 (68.9)
1750 (68.9)
1750 (68.9)
1750 (68.9)
• Depth
mm (in)
544 (21.4)
544 (21.4)
544 (21.4)
544 (21.4)
Weight, approx.
kg (lb)
390 (960)
390 (960)
480 (1058)
480 (1058)
Frame size
HI
HI
JI
JI
Minimum short-circuit current
4)
A
9200
8800/10400
16000
21000
1)
The breakers must always be switched ON and OFF by the sequence
control. An interlocking set 3WL9111-0BA21-0AA0 as described in
Catalog LV 10 should be provided for the bypass contactor to exclude
the risk of unintentional manual operation. Manual operation bypasses the
pre-charging circuit and can therefore destroy the Active Line Module.
2)
Information on higher capacities is included in the SINAMICS Low Voltage
Engineering Manual
.
3)
The specified power loss represents the maximum value at 100 % utilization.
The value is lower under normal operating conditions.
4)
Current required for reliably triggering protective devices.
© Siemens AG 2017