SIEMENS
7/132
Siemens D 21.4 · 2017
SINAMICS S120 drive system
Chassis format
Air-cooled Active Interface Modules in chassis format
7
■
Technical specifications
Line voltage 380 ... 480 V 3 AC
Active Interface Modules
6SL3300-7TE32-6AA0
6SL3300-7TE33-8AA0
6SL3300-7TE35-0AA0
Suitable for Active Line Module
• Rated power at 400 V
kW
132
160
235
300
- Air-cooled
6SL3330-7TE32-1AA3
6SL3330-7TE32-6AA3
6SL3330-7TE33-8AA3
6SL3330-7TE35-0AA3
- Liquid-cooled
–
–
–
6SL3335-7TE35-0AA3
Rated current
A
210
260
380
490
Bypass contactor
Included
Included
Included
Included
Current demand
• 24 V DC auxiliary power supply
A
0.17
0.17
0.17
0.17
• 230 V 2 AC
-
Inrush current
A
1.25
1.25
2.5
2.5
-
Holding current
A
0.6
0.6
1.2
1.2
DC link capacitance
of drive line-up, max.
1)
μ
F
41600
41600
76800
76800
Power loss, max.
2)
• At 50 Hz 400 V
kW
2.1
2.2
3.0
3.9
• At 60 Hz 460 V
kW
2.1
2.2
3.0
3.9
Cooling air requirement
m
3
/s (ft
3
/s)
0.24 (8.5)
0.24 (8.5)
0.47 (16.6)
0.47 (16.6)
Line/load connection
L1, L2, L3 / U2, V2, W2
Flat connector for
M10 screw
Flat connector for
M10 screw
Flat connector for
M10 screw
Flat connector for
M10 screw
• Conductor cross section, max. (IEC)
mm
2
2 × 185
2 × 185
2 × 185
2 × 185
PE/GND connection
2 × M10 nut
2 × M10 nut
2 × M10 nut
2 × M10 nut
• Conductor cross section, max. (IEC)
mm
2
2 × 185
2 × 185
2 × 185
2 × 185
Degree of protection
IP20
IP20
IP20
IP20
Dimensions
• Width
mm (in)
325 (12.8)
325 (12.8)
325 (12.8)
325 (12.8)
• Height
mm (in)
1400 (55.1)
1400 (55.1)
1533 (60.3)
1533 (60.3)
• Depth
mm (in)
355 (14.0)
355 (14.0)
544 (21.4)
544 (21.4)
Weight, approx.
kg (lb)
135 (298)
135 (298)
190 (419)
190 (419)
Frame size
FI
FI
GI
GI
Minimum short-circuit current
3)
A
6200
10500
10500
8000
1)
Information on higher capacities is included in the SINAMICS Low Voltage
Engineering Manual.
2)
The specified power loss represents the maximum value at 100 % utilization.
The value is lower under normal operating conditions.
3)
Current required for reliable triggering of the protective devices.
© Siemens AG 2017