SIEMENS
7/128
Siemens D 21.4 · 2017
SINAMICS S120 drive system
Chassis format
Air-cooled Active Line Modules in chassis format
7
■
Technical specifications
(continued)
Line voltage 500 ... 690 V 3 AC
Active Line Modules
6SL3330-7TG35-8AA3
6SL3330-7TG37-4AA3
6SL3330-7TG41-0AA3
6SL3330-7TG41-3AA3
Rated power
• At
I
rated DC
(50 Hz 690 V)
kW
630
800
1100
1400
• At
I
H DC
(50 Hz 690 V)
kW
620
705
980
1215
• At
I
rated DC
(50 Hz 500 V)
kW
447
560
780
965
• At
I
H DC
(50 Hz 500 V)
kW
450
510
710
880
• At
I
rated DC
(60 Hz 575 V)
hp
675
900
1250
1500
• At
I
H DC
(60 Hz 575 V)
hp
506
600
1000
1250
DC link current
• Rated current
I
rated DC
A
644
823
1148
1422
• Base-load current
I
H DC
1)
A
573
732
1022
1266
• Maximum current
I
max DC
A
966
1234
1722
2133
Infeed/regenerative feedback current
• Rated current
I
rated I
A
575
735
1025
1270
• Maximum current
I
max I
A
862
1102
1537
1905
Current demand
• 24 V DC auxiliary power supply
A
1.4
1.5
1.7
1.7
• 500 V AC
A
3.0
4.4
4.4
4.4
• 690 V AC
A
2.1
3.1
3.1
3.1
DC link capacitance
• Active Line Module
μ
F
7400
11100
14400
19200
• Drive line-up, max.
μ
F
59200
153600
153600
153600
Power loss, max.
2)
• At 50 Hz 690 V
kW
6.8
10.2
13.6
16.5
• At 60 Hz 575 V
kW
6.2
9.6
12.9
15.3
Cooling air requirement
m
3
/s (ft
3
/s)
0.78 (27.5)
1.08 (38.1)
1.08 (38.1)
1.08 (38.1)
Sound pressure level
L
pA
3)
(1 m) at 50/60 Hz
dB
70/73
71/73
71/73
71/73
Line connection
U1, V1, W1
Flat connector for M12
screw
Flat connector for M12
screw
Flat connector for M12
screw
Flat connector for M12
screw
• Conductor cross section, max. (IEC)
mm
2
4 × 240
6 × 240
6 × 240
6 × 240
DC link connection
DCP, DCN
4 × hole for M12
4 × hole for M12
4 × hole for M12
4 × hole for M12
• Conductor cross section, max. (IEC)
mm
2
Busbar
Busbar
Busbar
Busbar
PE1/GND connection
M12 screw
M12 screw
M12 screw
M12 screw
• Conductor cross section, max. (IEC)
mm
2
240
240
240
240
PE2/GND connection
2 × M12 screw
3 × M12 screw
3 × M12 screw
3 × M12 screw
• Conductor cross section, max. (IEC)
mm
2
2 x 240
3 x 240
3 x 240
3 x 240
Cable length, max.
4)
• Shielded
m (ft)
2250 (7382)
2250 (7382)
2250 (7382)
2250 (7382)
• Unshielded
m (ft)
3375 (11073)
3375 (11073)
3375 (11073)
3375 (11073)
Degree of protection
IP00
IP00
IP00
IP00
Dimensions
• Width
mm (in)
503 (19.8)
704 (27.7)
704 (27.7)
704 (27.7)
• Height
mm (in)
1475 (58.1)
1480 (58.3)
1480 (58.3)
1480 (58.3)
• Depth
mm (in)
540 (21.3)
550 (21.6)
550 (21.6)
550 (21.6)
Weight, approx.
kg (lb)
290 (639)
450 (992)
450 (992)
450 (992)
Frame size
HX
JX
JX
JX
Minimum short-circuit current
5)
A
8400
10500
16000
20000
1)
The base-load current
I
H DC
is the basis for a duty cycle of 150 % for 60 s
or
I
max DC
for 5 s with a duty cycle duration of 300 s.
2)
The specified power loss represents the maximum value at 100 % utilization.
The value is lower under normal operating conditions.
3)
Total sound pressure level of Active Interface Module and Active Line
Module.
4)
Total of all motor cables and DC link. Longer cable lengths for specific
configurations are available on request.
For additional information, please
refer to the SINAMICS Low Voltage Engineering Manual
.
5)
Current required for reliably triggering protective devices.